D-4

MAINTENANCE

D-4

SMOKE DETECTOR

The sensor will become contaminated over time. The
LED display (See Figure D.2, Item B) shows the cur-
rent degree of sensor contamination.

Contamination status of LED display:

• 0-69%: OK

• 70-98%: sensor needs to be replaced (LED display

flashes)

99%: system will enter into fire alarm phase

• During use, check the status of the LED display reg-

ularly.

• Replace the sensor when the contamination level has

reached 70%.

SLIDING VALVES

In order to function properly, the sliding valves must be
inspected regularly. See Figure D.3.

AEROSOL

The Flame Guardian™ must be inspected periodically
in accordance with the national fire protection associa-
tion requirements or the local authorities having juris-
diction. See Figure D.4.

NOTE: Place a label on the Flame Guardian™ stating

the installation date and testing date.

GUARDIAN CONTROL™ SOLUTIONS

FIGURE D.2

A

B

C

D

E

F

Poor maintenance will eventually
lead to the fire alarm being activated
incorrectly. Regular inspections are
necessary.

-----------------------------------------------------------------------

WARNING

FIGURE D.3

Every 6
Months

Pneumatics

Check connections.

Component

Action

Frequency:

X

Electrical wiring

Check connections.

X

Bolts and nuts

Check for correct tightening.

X

FIGURE D.4

:

y

c

n

e

u

q

e

r

F

n

o

i

t

c

A

t

n

e

n

o

p

m

o

C

Every 12
Months

Every 10
Years

Metal holder

Check for damage, corrosion

and correct position.

X

Support bracket

Check for damage, corrosion

and correct position.

X

System wiring
connections and
circuit

Check proper wiring and
circuit.

X

Flame Guardian™
internal activation

Check internal activation;
See Flame Guardian™ Functional
Test in Installation Section.

X