beautypg.com

Installation, A-9 physical dimensions and properties, Shipping data – Lincoln Electric P709 GUARDIAN CONTROL SOLUTIONS User Manual

Page 16: Technical data, Dimensions

background image

A-9

INSTALLATION

GUARDIAN CONTROL™ SOLUTIONS

A-9

PHYSICAL DIMENSIONS AND PROPERTIES

TECHNICAL SPECIFICATIONS - SOLENOID VALVE

FIRE SUPPRESSION

MATERIAL BODY

Aluminum Alloy

DIMENSIONS

See Below

SHIPPING DATA

GROSS WEIGHT

PACKING DIMENSIONS

10.0 x 5.9 x 3.5 in. (255 x 150 x 90 mm)

HARMONIZED TARIFF CODE

8536.4110.90

COUNTRY OF ORIGIN

TECHNICAL DATA

OPERATING VOLTAGE

24 V AC +/- 15%

POWER CONSUMPTION

3.5 W

PROTECTION CLASS

IP 65

VALVE TYPE

3 ports, 2 positions

PORT SIZE

3/8 inch

THREAD TYPE

G

ACTING TYPE

NC (normally closed)

ELECTRICAL ENTRY TYPE

Terminal

COMPRESSED AIR TUBE CONNECTION

ø 12 mm

OPERATING PRESSURE

21-114 psi (0.15-0.8 mPa)

ACTIVATING TIME

<0.05 seconds

FREQUENCY

Maximum 5 cycles/second

OPERATING TEMPERATURE

MINIMUM

MAXIMUM

-4º F (-20ºC)

158º F (+70ºC)

A

P R

A

P

R

A

C

B

mm

inch

A

27

1.06

B

109

4.29

C

120

4.72

DIMENSIONS