Operation, B-10, B-10 main controls manual call point – Lincoln Electric P709 GUARDIAN CONTROL SOLUTIONS User Manual
Page 60: Figure b.9 – manual call point

B-10
OPERATION
B-10
MAIN CONTROLS
MANUAL CALL POINT
When a fire is detected, the fire detection and sup-
pression system can be activated manually through a
manual call point.
• The manual call point comes with a separate key for
restarting.
To activate the manual call point, proceed as follows.
• Use the
PUSH
and
PULL
handle as indicated.
Reset
To reset the activation handle on the manual call point,
proceed as follows.
• Unlock and open box using the key.
• Place switch in initial
STANDBY
position (down).
• Close and relock the box.
NOTE: Store the key separately from the manual call
point to prevent improper use.
GUARDIAN CONTROL™ SOLUTIONS
FIGURE B.8 – MAIN CONTROLS
How to:
Action:
Display:
Comments:
Test lamps.
Push 2 top
buttons.
All LEDs and
display will
illuminate for
one second.
Panel is in normal
conditions.
Reset alarm
condition.
Determine
cause e.g. fire
and only push
SYSTEM
RESET
after cause
has been
settled.
Panel will go
to normal and
display will
show
PLYMOVENT
.
Program switch in
RUN
. This action will
undo any alarm
immediately.
Silence alarm
sounder.
Push
SIGNAL
SILENCE
.
LED
OUTPUT
1
will go out.
Only silence alarm
when cause has
been determined
and appropriate
actions or warnings
are given.
Reset trouble
condition
POWER
TROUBLE
or
SYSTEM
TROUBLE
.
Determine the
cause and
remove e.g.
open circuit or
resolve low
battery
voltage.
When trouble
is removed
indicator will
automatically
return to
normal.
Silence trouble
buzzer.
Press button
SIGNAL
SILENCE
.
Only silence alarm
when cause has
been determined
and appropriate
actions or warnings
are given.
Go to normal
standby
position.
Switch to
position
RUN
.
Display shows
PLYMOVENT
and
power LED is
green.
System is now in
operation.
FIGURE B.9 – MANUAL CALL POINT