Page 60: Figure b.9 – manual call point

background image

B-10

OPERATION

B-10

MAIN CONTROLS

MANUAL CALL POINT

When a fire is detected, the fire detection and sup-
pression system can be activated manually through a
manual call point.

• The manual call point comes with a separate key for

restarting.

To activate the manual call point, proceed as follows.

• Use the

PUSH

and

PULL

handle as indicated.

Reset

To reset the activation handle on the manual call point,
proceed as follows.

• Unlock and open box using the key.

• Place switch in initial

STANDBY

position (down).

• Close and relock the box.

NOTE: Store the key separately from the manual call

point to prevent improper use.

GUARDIAN CONTROL™ SOLUTIONS

FIGURE B.8 – MAIN CONTROLS

How to:

Action:

Display:

Comments:

Test lamps.

Push 2 top
buttons.

All LEDs and
display will
illuminate for
one second.

Panel is in normal
conditions.

Reset alarm
condition.

Determine
cause e.g. fire
and only push

SYSTEM

RESET

after cause
has been
settled.

Panel will go
to normal and
display will
show

PLYMOVENT

.

Program switch in

RUN

. This action will

undo any alarm
immediately.

Silence alarm
sounder.

Push

SIGNAL

SILENCE

.

LED

OUTPUT

1

will go out.

Only silence alarm
when cause has
been determined
and appropriate
actions or warnings
are given.

Reset trouble
condition

POWER

TROUBLE

or

SYSTEM

TROUBLE

.

Determine the
cause and
remove e.g.
open circuit or
resolve low
battery
voltage.

When trouble
is removed
indicator will
automatically
return to
normal.

Silence trouble
buzzer.

Press button

SIGNAL

SILENCE

.

Only silence alarm
when cause has
been determined
and appropriate
actions or warnings
are given.

Go to normal
standby
position.

Switch to
position

RUN

.

Display shows

PLYMOVENT

and

power LED is
green.

System is now in
operation.

FIGURE B.9 – MANUAL CALL POINT