Operation, Fire action procedure, Warning – Lincoln Electric P709 GUARDIAN CONTROL SOLUTIONS User Manual
Page 61: Attention, Caution

B-11
OPERATION
B-11
FIRE ACTION PROCEDURE
In case of fire
When a fire is detected, the system can be activated
manually through a manual call point (See Manual
Call Point).
AUTOMATIC DETECTION OF FIRE
In the event of a fire, the system reacts as follows.
1. The display shows ALARM and indicates fire zone.
2. A Red alarm LED in specific zone flashes.
Audible/visible indicators are switched on and the
fire alarm sounder is activated.
3. The system control panel stops the fan, closes the
sliding valves and releases the compressed air
through the solenoid valve.
4. Five seconds after fire alarm, the Flame
Guardian™(s) is/are activated; LEDs
OUTPUT
1
TO 4 will be lit.
NOTE: The Flame Guardian™ extinguishing material
is extremely fine. In case of fire, it may seem
like smoke escapes through the seams of the
filter system, but most commonly it is the extin-
guishing material which is harmless to environ-
ment and people.
POST-FIRE PROCEDURE
Statiflex Filter Bank and Flame Guardian™
After any fire incident, the entire installation must
be inspected and released by a skilled and autho-
rized service engineer.
The following activities are strictly reserved to
skilled and authorized service engineers.
1. Inspect the filter and hopper for glowing materials
before continuing.
2. Inspect the filter cartridges. If they are damaged by
fire or any cartridge less than 20 in. (50 cm) proxim-
ity of the aerosol release opening must be replaced.
3. Follow maintenance procedure on spark detectors
(See Spark Detector in Maintenance Section).
4. Follow maintenance procedure on smoke detector
(See Smoke Detector in Maintenance Section).
5. Follow maintenance procedures for the Heat
Detectors.
The Flame Guardian™ modules get hot from the
release of the aerosol. Allow the modules to cool down
before replacement.
6. Disconnect power to the Guardian™ Panel.
7. Replace the Flame Guardian™ module(s).
8. Perform the post installation checks of all separate
components.
9. Perform the Commissioning Checklist.
10. The used Flame Guardian™ modules can be dis-
posed of as nonhazardous waste in accordance
with state, local and federal laws.
GUARDIAN CONTROL™ SOLUTIONS
Always comply with the legal fire
safety procedures and respect
instructions from the fire safety coor-
dinator.
-----------------------------------------------------------------------
WARNING
To avoid re-ignition of the fire and to
prevent consequential damage, keep
filter closed for at least 30 minutes
from the time the fire suppression
agent is released.
-----------------------------------------------------------------------
WARNING
During inspection and maintenance, always use
Personal Protective Equipment (PPE) to avoid
injury. This also applies for persons who enter the
work area.
-----------------------------------------------------------------------
WARNING
Do NOT start maintenance before receiving per-
mission from authorized personnel.
------------------------------------------------------------------------
ATTENTION
Turn Guardian™ Fire Detection Panel to “Manual”
before changing filter or suppression will activate.
-----------------------------------------------------------------------
CAUTION