INSTALLATION

GUARDIAN CONTROL™ SOLUTIONS

A-21

FUNCTIONAL TESTING (GENERAL)

NOTE: Before performing any functional testing make

sure the Flame Guardian™ is disconnected to
prevent unwanted discharge. See Wiring
Diagram.

To perform any functional test, the following instruc-
tions should be followed.

1. Ensure that the Flame Guardian™ module(s) is/are

not connected to a power source.

2. Perform the desired Functional Test. Sound alarm

will go off.

3. Check fire zone.

4. Press the

SIGNAL SILENCE

button on the

Guardian™ Panel to suppress alarm.

5. Press the

SYSTEM RESET

button.

To proceed with testing:

• Restart procedure.

If testing has been completed:

• Reconnect the Flame Guardian™ module(s).

• Make sure the panel is in RUN mode.

FUNCTIONAL TEST (SLIDING VALVES)

The sliding valves can be tested manually by pushing
the test button (A) on the 5/2 solenoid valve.

• Functionally test both sliding valves.

• Refer to the Pneumatic Diagram for more details

FIGURE A.16

A