beautypg.com

Installation – Lincoln Electric P709 GUARDIAN CONTROL SOLUTIONS User Manual

Page 49

background image

A-42

INSTALLATION

GUARDIAN CONTROL™ SOLUTIONS

A-42

Smoke Detector

Manual Call Point and Fire Alarm Sounder

Flame Guardian™

Solenoid Valve

#

Check

OK

1. Is the smoke detector placed in the filter out-

let duct?

2. Is the LED display of the smoke sensor visi-

ble to read the contamination level? If not, an
external warning device, connected to the
detector circuit board terminal 16 and 17 is
recommended to monitor the sensor pollu-
tion.

3. Is the sampling tube correctly installed in

relation to the airflow?

4. Is the smoke detector sensor checked for

contamination level? In case of contamina-
tion level >69%, also indicated by a flashing
LED display, sensor must be replaced.

5. Is the End Of Line Resistor placed over ter-

minal 11 and 12 and in line with the
Guardian™ Panel?

6. Is the smoke detector connected to Zone 3 of

Guardian™ Panel?

7. Is the smoke detector being functionally test-

ed by test spray and alarm/reset button? Is
the signal being monitored by Guardian™
Panel?

8. Is the smoke detector being reset?

#

Check

OK

1. Are the manual call points marked or placed

close to the Guardian™ Panel in order to
avoid confusion with the general manual
alarm boxes of the building?

2. Is the End Of Line Resistor that was placed

in the manual call point in line with the
Guardian™ Panel?

3. Are the fire alarm sounders placed close to

the Guardian™ Panel and fitted with the cor-
rect End Of Line resistor 5k1?

4. Is the sounder set to your local tone?

5. Is sound level set to the maximum?

6. Is the manual call point being functionally

tested and monitored by the Guardian™
Panel?

7. Is the fire alarm sounder being tested and

activated by Guardian™ Panel?

#

Check

OK

1. Are Flame Guardian™ modules undam-

aged?

2. Is the correct number of Flame Guardian™

modules being installed?

3. Are the Flame Guardian™ modules placed in

the correct locations?

4. Are the Flame Guardian™ modules pushed

back to the middle stop of the mounting
bracket to secure a 10° downward release
angle?

5. Are all nuts and bolts secure?

6. Are the cables tension free, well guided and

secured by the cable glands/clamps?

7. Are the cable glands secure?

8. Has the internal wiring/electrical activation

been checked by measuring resistance over
the internal heating device of the Flame
Guardian™ with a current less than 5 mil-
liamps? The resistance must be 2 ohm.

9. Are, in combination with Guardian™ Panel,

the End Of Line resistor-diodes of 5k1 placed
in each junction box and the Flame
Guardian™ connected to output 2, 3 or 4?

#

Check

OK

1. Is the 3/2 solenoid valve mounted between

compressed air reducer (CAR kit) and filter?

2. Is the solenoid electrically and pneumatically

wired properly? When the solenoid is discon-
nected from power, the air from the com-
pressed air tanks of the filter system should
be released.

3. Is the solenoid functionally tested after a fire

test alarm in the complete system set up?