Installation – Lincoln Electric P709 GUARDIAN CONTROL SOLUTIONS User Manual

Page 37

background image

A-30

INSTALLATION

GUARDIAN CONTROL™ SOLUTIONS

A-30

All connections for field wiring are to the terminal strips
along the top and bottom of the circuit board. See
Figure A.27
. Also See Wiring Diagram.

Cables to be used:

• 5 x 20 AWG shielded cable for detectors and

manual call point

• 5 x 20 AWG normal cable for other wiring

The resistance of any core of any cable should not
exceed 25 ohm(>1640 ft for 20 AWG).

To connect the cables to the Guardian™ Panel, use
suitable metal cable glands fitted to the knock-outs
provided.

1. Connect all cables to the Guardian™ Panel in accor-

dance with the Electrical Wiring Diagram.

The wiring of the detectors, manual call point, Flame
Guardian™ and fire alarm sounder is monitored for
open circuit fault conditions. See Wiring Diagram.

BATTERY PACKS

The Guardian™ Panel is fitted with
battery leads wired to the circuit board
to connect the two battery packs.

1. Place both battery packs inside the Guardian™

Panel.

2. Connect them to the battery leads.

NOTE: It is extremely important for the polarity of the

batteries to be connected correctly. Incorrect
connections could damage the control panel.

MAIN SUPPLY

The main supply of 115V/230V AC must be connected
to a dedicated circuit. See Wiring Diagram.

1. Connect the Guardian™ Panel to the main in accor-

dance with the Electrical Wiring Diagram.