beautypg.com

Grounding instructions, Safety instructions – Darex XPS-16 Operating Instructions User Manual

Page 4

background image

4

Fig .1

Grounding

methods

Grounded

Means

Cover of

grounded

outlet box

Grounding Pin

Grounding Pin

Metal

Screw

(A) (B)

(C)

(D)

Safety Instructions

Safety Instructions

GROUNDING INSTRUCTIONS

For all grounded, cord connected tools:

In the event of a malfunction or breakdown, grounding provides a
path of least resistance for electric current to reduce the risk of
electric shock. This tool is equipped with an electric cord having

an equipment-grounding conductor and a grounding plug. The
plug must be plugged into a matching outlet that is properly in-
stalled and grounded in accordance with all local codes and ordi-
nances. Do not modify the plug provided-if it will not fit the outlet,
have the proper outlet installed by a qualified electrician. Im-
proper connection of the equipment-grounding conductor can
result in a risk of electric shock. The conductor with insulation,
having an outer surface that is green with or without yellow
stripes, is the equipment-grounding conductor. If repair or re-
placement of the electric cord or plug is necessary, do not connect
the equipment-grounding conductor to a live terminal. Check with
a qualified electrician or serviceman if the grounding instructions
are not completely understood, or if in doubt as to whether the
tool is properly grounded. Use only 3-wire extension cords that
have 3-prong grounding plugs and 3-pole receptacles that accept
the tool’s plug. Repair or replace damaged or worn cord immedi-

ately. See Table 1. Minimum Gauge Cords below.


Grounded, cord-connected tools intended for use on a
supply circuit having a nominal rating less than 150 volts:
This tool is intended for use on a circuit that has an outlet that
looks like the one illustrated in Figure A. The tool has a grounding
plug that looks like the plug illustrated in Figure A. A temporary
adapter which looks like the adapter illustrated in Figures B and C,
may be used (except in Canada) to connect this plug to a 2-pole
receptacle as shown in Figure B if a properly grounded outlet is
not available. The temporary adapter should be used only until a
qualified electrician can install a properly grounded outlet. The
green colored rigid ear lug, etc. extending from the adapter must
be connected to a permanent ground such as a properly grounded
outlet box. See Fig. 1. Grounding methods below.




Grounded cord-connected tools intended for use on a sup-
ply circuit having a nominal rating between 150-250 volts
inclusive:
See Table 1. Minimum Gauge Cords below.

Table 1 Minimum Gauge Cords