FEC DSP1500 Main Unit User Manual
Page 58

enFORCE
DSP1500 Main Unit Hardware Manual
(Rev. 4.0)
PAGE 5 - 18
Chapter 5: Control Interfaces
5.4.1 Component Descriptions
Fieldbus Interface Connectors
Bus IN
Pin No.
Signal
Description
Housing
PE Protective
Earth
Ground
1
DO1 Data
Output
2
DI1 Data
Input
3
GND Signal
Ground
4
NC -
5
NC -
6
/DO1 Inverted
Data
Output
7
/DI1 Inverted
Data
Input
8
NC -
(9 pin male D-sub)
9
NC -
Bus OUT
Pin No.
Signal
Description
Housing PE
Protective
Earth
Ground
1
DO2
Data
Output
2
DI2
Data
Input
3
GND
Signal
Ground
4
NC
-
5
GND
Signal
Ground
6
/DO2
Inverted
Data
Output
7
/DI2
Inverted
Data
Input
8
NC
-
(9 pin female D-sub)
9 RBST
*
*Always terminate RBST to ground if it is not the last module on the bus. If the RBST is not
connected to ground, the interface will automatically terminate the bus.
Baud Rate Switch
The module supports 2Mbit/s and 500Kbit/s operation. To select the
desired baud rate, just move the jumper cap to the corresponding
location.
Baud rate must be selected before power is on and cannot be changed during operation.
Status LEDs
No. LED Color
Description
1
CC/RC
Green
Cable connection is good & master not in reset
2
BA Green
Bus Active
3 RD Yellow
Remote Bus Disabled
4 TR Green
PCP - Communication active.
Hold Time = 500ms
5
1
9
6
1
5
6
9