beautypg.com

Table 8-4. koyo plc write control bytes, 7 set-up procedure – Micromod Micro-DCI: 53MC5000 PLC AND PRINTER INTERFACES User Manual

Page 97

background image

Table 8-4. Koyo PLC Write Control Bytes

Title

Definition

DDI-A DDI-B

Set

By

De-

fault

PLC Address

It is the address of the PLC to be accessed. B674

B650

User

0

Starting PLC Memory
Address (Low)

The two byte PLC memory address that
states where to start writing data into the
PLC memory. Each byte is a decimal
number; however, both bytes together
function as a 16 bit unsigned binary integer
(see Koyo Read Control Bytes for example).

B675

B651

User

0

Starting PLC Memory
Address (High)

B676

B652

User

0

Number of L-Words
to Write

The number of L-words that are to be
written to the PLC.

B677

B653

User

0

Number of C-Words
to Write

The number of C-words that are to be
written to the PLC.

B678

B654

User

0

Memory Type

This byte must be 31.

B679

B655

User

0

Communications
Error*

0 = no errors. 255 = timeout error - a
timeout error indicates no response came
back from the PLC. 254 = bad checksum
(CRC) - a bad checksum indicates even
though the frame was formatted properly,
the data can not be used. 253 = bad
message - bad message indicates that
errors were found in the predictable portion
of the message from the PLC. 252 and 251
= PCS hardware malfunction.

B682

B658

Soft-
ware

0

Error Count*

This byte is a running total of the non-zero
Communications Error Codes.

B683

B659

Soft-
ware

0

*User can reset by writing zeros into the datapoints.

8.7 SET-UP PROCEDURE

The Koyo PLC documentation must be referenced to install and configure the PLC.

1. Reference the 53MC5000 Process Control Station book listed in the Preface to install the PCS.

2. See Section 2 of this book to mount the RS-232/485 ITB and cable connect it to the PCS.

3. See Figure 8-2 in this section to fabricate a custom RS-232 cable required to connect J1 to the

PLC or see Figure 8-3 in this section to fabricate a custom RS-485 (422) cable required to con-
nect TB2 to the PLC.

4. See Section 2 of this book for the required power connections to the RS-232/485 ITB.

5. Define the PLC memory map as determined from the quantity of L-bytes and C-words to be

transferred between the PCS and PLC. The size and address locations of the PCS L- and C-
memory areas are defined in Section 3.1 and illustrated in Figures 3-1 and 3-2.

Section 8. Koyo Mode

KOYO

8-5