7.0 SIEMENS S5 MODE

7.1 PURPOSE

The Siemens interface application permits data transfers between the Process Control Station
(PCS) and a Siemens Programmable Logic Controller (PLC) via the 3964 protocol. The PCS sup-
ports the following commands for both read and write operations:

1. D - Data Block

2. A - Absolute Address

The PCS supports the following commands for read-only operations:

3. Z - Counter Locations

4. E - Input Bytes

5. A - Output Bytes

6. M - Flag Bytes

The Data Block and Absolute Address commands handle data in 16 bit words and can be used for
L- and/or C-type data. L-data quantities must be even numbers (odd numbers will be decremented
by one). The Counter Locations command reads data in 16 bit words. The upper 6 bits are
masked out and the resulting 10 bit words are handled as C-type data. The remaining three com-
mands handled data in bytes and can only be used with L-type data.

The maximum data transfer in either direction is 128 bytes, which corresponds to 64 PCS L-bytes
and 32 PCS C-words.

7.2 INSTALLATION CONFIGURATION

As shown in Figure 7-1, communication between the PCS and Siemens PLC is point-to-point.

Figure 7-1. Point-to-Point Installation Configuration

53MC5000
PCS

RS-232/485
ITB

SIEMENS
PLC
COMPLEX

Section 7. Siemens S5 Mode

SIEMENS

7-1