Micromod Micro-DCI: 53MC5000 PLC AND PRINTER INTERFACES User Manual
Page 13
• An available Expansion board slot for the DDI-A APB (slot 3) and/or the DDI-B APB (slot 1).
To determine the Expansion board option card complement, display slot location datapoints
B095 through B099 (for slots 1 through 5 respectively). Option card codes are 128 = Mi-
croLink, 129 = APB, 1 = 6DI/4DO, 2 = Single Channel Analog Input, 3 = Multi-Channel Ana-
log I/O, 4 = 16DI/DO, and 5 = HART Modem. One exception is the 6DI/4DO option card
code (1), which may not appear in the displayed datapoint even if the card occupies a slot lo-
cation. (Instructions to remove and install hardware in the PCS are provided in Table 10-1,
Parts Replacement.)
• An RS-232/485 ITB with ITB-to-PCS cable for each DDI-A/B option. (Instructions to install
an ITB are provided in Section 2.)
• A custom fabricated ITB-to-PLC cable or ITB-to-serial/parallel converter cable for the printer.
These cables are described in the applicable PLC/printer section (Sections 4 through 9) that
follows.
It should be noted that an APB at the proper firmware level in slot 3 can be bridged with a Connec-
tor board to a HART Option Modem card in slot 5 for DDI-A Printer or PLC operation and for HART
Multi-Channel Analog operation.
1.4 RS-232/485 ITB SPECIFICATIONS
Specifications for the RS-232/485 ITB are provided in Table 1-1 as follows:
Table 1-1. RS-232/485 ITB (686B720) Specifications
Characteristic
Specification
Environmental Characteristics
Operating Temperature Range
4
° - 52°C (40° - 125°F)
Relative Humidity
10% to 90% maximum
Shock and Vibration
0.5 G (Gravity - 32 ft/sec/sec)
Input Power
Input Power Requirements
12 to 26 V dc at 100 mA maximum
Section 1. Introduction
INTRO
1-3