GROUNDING

Installations are expected to have access to a high quality, noise-free

point of earth reference. Connection should be through a low

resistance (less than one ohm) lead wire directly to the installation’s

point of earth reference which can be an independent grounding rod or

ground grid mesh that penetrates the permanent moisture level below

the frost line in accordance with Article 250 of ANSI/NFPA 70, the

National Electrical Code, or other code(s) acceptable to the authority

having jurisdiction over the installation.

COMMON BUS BAR

Use of a common bus bar that is connected to the earth ground through

a low resistance (less than one ohm) lead wire is recommended to

minimize potential voltage differences that may occur as a result of

ground loops, e.g., potential differences between separate power

grounds, signal grounds, etc.

METAL CONDUIT

In noisy locations, the power wiring should be enclosed in metal

electrical conduit and not routed in close proximity to signal wiring.