Figure 5-4. opto 22 analog boards – Micromod Micro-DCI: 53MC5000 PLC AND PRINTER INTERFACES User Manual
Page 53

CONTIGUOUS ANALOG BOARDS 32 - 39
BOARD
ADDRESS
MODULE NUMBER
NUMBER OF
ACTIVE
CONTIGUOUS
BOARDS
B675/B651
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
NUMBER OF ANALOG MODULES PER BOARD DDI-A B676 [DDI-B B652]. (E.G., IF B676 [OR B652] = 12,
THEN 12 MODULES PER BOARD AND MAXIMUM POPULATION OF 60 MODULES ON 5 BOARDS
[BOARDS X MODULES CAN NEVER EXCEED 64].)
(DDI-A AND DDI-B DATAPOINTS ARE SHOWN VERTICALLY BELOW)
32
C C
7 6
0 4
4 0
C C
7 6
0 4
5 1
C C
7 6
0 4
6 2
C C
7 6
0 4
7 3
C C
7 6
0 4
8 4
C C
7 6
0 4
9 5
C C
7 6
1 4
0 6
C C
7 6
1 4
1 7
C C
7 6
1 4
2 8
C C
7 6
1 4
3 9
C C
7 6
1 5
4 0
C C
7 6
1 5
5 1
E
M
P
T
Y
E
M
P
T
Y
E
M
P
T
Y
E
M
P
T
Y
1
DDI-A B677 [DDI-B B653] = BOARD MODULE OUTPUTS (E.G., IF B677 [OR
B653] = 8, THEN C704 [C640] TO C711 [C647] ARE OUTPUT MODULE SLOTS
AND C712 [C648] TO C715 [C651] ARE INPUT MODULE SLOTS.
33
C C
7 6
1 5
6 2
C C
7 6
1 5
7 3
C C
7 6
1 5
8 4
C C
7 6
1 5
9 5
C C
7 6
2 5
0 6
C C
7 6
2 5
1 7
C C
7 6
2 5
2 8
C C
7 6
2 5
3 9
C C
7 6
2 6
4 0
C C
7 6
2 6
5 1
C C
7 6
2 6
6 2
C C
7 6
2 6
7 3
E
M
P
T
Y
E
M
P
T
Y
E
M
P
T
Y
E
M
P
T
Y
2
SLOT ADDRESSING CONTINUES FROM PREVIOUS BOARD.
DDI-A B677 [DDI-B B653] = 8; THEREFORE, C716 [C652] TO C723 [C659] ARE
OUTPUT MODULE SLOTS AND C724 [C660] TO C727 [C663] ARE INPUT
MODULE SLOTS.
34
•
•
•
39
(IF 5 BOARDS ARE USED WITH 12 MODULES EACH, THEN BOARD
ADDRESSES ARE 32 TO 36. ALSO, SLOT ADDRESSING ALWAYS CONTINUES
FROM PREVIOUS BOARD.)
3
•
•
•
8
INPUT PROBE TYPES
TYPE
PROBE
TYPE
PROBE
0
16
NO TEMPERATURE PROBE
6
16
TYPE R THERMOCOUPLE (AD17T)
1
16
ICTD PROBE (AD4 MODULE)
7
16
TYPE S THERMOCOUPLE (AD17T)
2
16
10 OHM RTD PROBE (AD14T)
8
16
TYPE T THERMOCOUPLE (AD18T)
3
16
100 OHM RTD PROBE (AD10T)
9
16
TYPE E THERMOCOUPLE (AD19T)
4
16
TYPE J THERMOCOUPLE (AD5/AD5T)
A to
F
16
RESERVED
5
16
TYPE K THERMOCOUPLE (AD8/AD8T)
PROBE TYPE SELECTION (A MAXIMUM OF 4 TYPES CAN BE SELECTED FOR THE INPUT MODULES OF
THE 8 ANALOG BOARDS)
CHANNEL DATAPOINT
LEFT DIGIT
RIGHT DIGIT
DDI-A
B679
PROBE TYPE FOR BOARDS 33 AND 37
PROBE TYPE FOR BOARDS 32 AND 36
DDI-B
B655
PROBE TYPE FOR BOARDS 33 AND 37
PROBE TYPE FOR BOARDS 32 AND 36
DDI-A
B680
PROBE TYPE FOR BOARDS 35 AND 39
PROBE TYPE FOR BOARDS 34 AND 38
DDI-B
B656
PROBE TYPE FOR BOARDS 35 AND 39
PROBE TYPE FOR BOARDS 34 AND 38
EXAMPLES: TYPE 8 PROBE FOR BOARDS 33 AND 37 AND TYPE 4 PROBE FOR BOARDS 32 AND 36 =
84
16
. SEE APPENDIX A; 84
16
= 132
10
. ENTER 132 IN B679 [OR B655].
TYPE 5 PROBE FOR BOARDS 35 AND 39 AND TYPE 6 PROBE FOR BOARDS 34 AND 38 = 56
16
.
SEE APPENDIX A; 56
16
= 86
10
. ENTER 86 IN B680 [OR B656].
USE PROBE TYPE 0 FOR ALL ANALOG INPUTS OTHER THAN THERMOCOUPLES OR IF THERMOCOUPLE
INPUT PROBE TYPES GIVEN ABOVE ARE MIXED ON A SINGLE BOARD. IF INPUT PROBE TYPES ARE
MIXED ON A SINGLE BOARD, THE READ ANALOG INPUTS (76 [L]) COMMAND MUST BE USED AND THE
INPUT VALUES ARE RANGED BY THE PCS AS -819 TO 3276, REPRESENTING 0 TO 100% OF INPUT.
Figure 5-4. OPTO 22 Analog Boards
Section 5. OPTO 22 Mode
OPTO