Table 6-3. Control and Status Bytes for PCS Modbus Master
Title
Definition
DDI-A DDI-B
Set
By
De-
fault
Setup
Error
It indicates the following: 0 = No Error, 1 = L-bytes to
read > 64, 2 = C-words to read > 64, 3 = L-bytes to write
> 64, 4 = C-words to write > 64, 5 = Invalid Function
Code, 6 = Write command 6 specifies more than 1 word
of L or C data, 10 = Scan Time at 0. These error codes
cause DDI channel operation to halt.
B684
B660
Soft-
ware
0
Scan
Time
It is the PCS time period for the read and write phases
of a PCS-PLC transaction. It is entered as a number
from 1 to 255 which represents 100 to 25,500 ms. (See
Section 3.7.)
B685
B661
User
0
Scan
Overruns
Counter*
This counter is incremented each time the read-write
phases exceed the specified Scan Time. It indicates the
Scan Time should be increased. (See Section 3.7.)
B686
B662
Soft-
ware
0
*User can reset by writing zeros into the datapoints.
Table 6-4. Read Control Bytes for PCS Modbus Master
Title
Definition
DDI-A DDI-B
Set
By
De-
fault
PLC Address
It is the address of the PLC to be accessed. B664
B640
User
0
Starting PLC Memory
Address (Low)
The two byte PLC memory starting address.
Each byte is a decimal number; however,
both bytes together function as a 16 bit
unsigned binary integer, e.g., the PLC
hexadecimal address 4180
16
would be
entered as 65
10
in the high byte B666 [or
B642] and 128
10
in the low byte B665 [or
B641]. (See Appendix A for decimal
conversions.)
B665
B641
User
0
Starting PLC Memory
Address (High)
B666
B642
User
0
Number of L-Bytes to
Read
The number of L-bytes that are to be
accessed from the PLC.
B667
B643
User
0
Number of C-Words
to Read
The number of C-words that are to be
accessed from the PLC.
B668
B644
User
0
Function Code
It is the read command function code as
follows:
1 = Read Output Status (L)
2 = Read Input Status (L)
3 = Read Holding Registers (C - PLC
registers may contain L-values.)
4 = Read Input Registers (C - PLC
registers may contain L-values.)
B669
B645
User
0
1 of 2
Section 6. MODBUS RTU Mode