beautypg.com

Chapter 6, Aasicj – Advantech 5000 Series User Manual

Page 92

background image

Chapter 6

$aaSiCj

Name

Specified RTD Data In

Description Returns the input value of a specified channel for a

specified RTD input module of a specified system in
engineering units only.

Syntax $aaSiCj(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
interrogate.

SiCj identifies the desired slot i (i:0 to 3) and the desired
channel j (j:0 to 2) of the module you want to interrogate.

(cr) is the terminating character, carriage return (0Dh).

Response. >(data)(cr) if the command is valid.

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.

> delimiter character indicating a valid command was
received.

? delimiter character indicating the command was
invalid.

aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.

(data) is the input value in engineering units of the
specified channel for the specified RTD input module of
the specified system. If (data)=“ ”, it means the channel
is invalid.

(cr) is the terminating character, carriage return (0Dh).




ADAM-5000

6-27