Advantech 5000 Series User Manual
Page 121

Command Set 5017/5018
Analog Input
$aaSi9shhhh
Example
command: $07S29+0042(cr)
response: !07(cr)
The command increases the CJC offset value of the
analog input module in slot 2 of the system at address
07h with 66 counts (42 hex) which equals about 0.6°C.
Note:
An analog input module requires a maximum of 2
seconds to perform auto calibration and ranging after it
receives a CJC Calibration command. During this
interval, the module cannot be addressed to perform
any other actions.
6-56
ADAM-5000