$aaSiØ(data)

Name

Set Digital filter Scale

Description Set the filter seconds to start to measure the input signal.

Syntax $aaSiØ(data)(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system which is to be
calibrate.

Si identifies the sepcified slot.

Ø is the command for setting digital filter scale.

(data) represents filter secends from 8µs~65000 µs. Be
aware that (data) has 5 characters.

(cr) is the terminating character, carriage return (0Dh)

Response !aa(cr)

if the command is valid.

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax error
or communication error or if the specified address does
not exists.

! delimiter character indicating a valid command was
received.

? delimiter character indicating the command was
invalid.

aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.

(cr) is the terminating character, carriage return (0Dh)










ADAM-5000