Command Set 5017H/5017UH
Analog Input

#aaSi

the interrogated module of the specified system. The
(dddd) from all channels is shown in sequence from 7 to
0. If (dddd)=” “, it means the channel is invalid.

(cr) is the terminating character, carriage return (0Dh).


Example

command: #35S3(cr)

response: +6.000 +7.000 +8.125 +4.250 +10.000
+8.500 +7.675 +5.445 (cr)

The command requests the ADAM-5017H / 5017UH
module in slot 3 of the ADAM-5000 system at address
35h to return the input values of all channels.

The analog input module responds with the input values
of all channels, in sequence from 0 to 7: +6.000, +7.000,
+8.125, +4.250, +10.000, +8.500, +7.675, +5.445.




















6-68

ADAM-5000