beautypg.com

Aasicj – Advantech 5000 Series User Manual

Page 113

background image

Command Set 5017/5018

Analog Input

#aaSiCj

Name

Specified Analog Data In

Description Returns the input value of a specified channels for a

specified analog input module of a specified system in
engineering unit only.

Syntax #aaSiCj(cr)

# is a delimiter character.

aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
interrogate.

Si identifies the I/O slot you want to interrogate.

Cj identifies the channel you want to read.

(cr) is the terminating character, carriage return (0Dh)

Response >(data)

if the command is valid.

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.

> is a delimiter character indicating a valid command was
received.

? delimiter character indicating the command was
invalid.

(data) is the input value in engineering units of the
specified channel for a specified analog input module of
the specified system. If (data) = “

”, it means the

channel is invalid.

(cr) is the terminating character, carriage return (0Dh)



6-48

ADAM-5000