Installation Guideline

2.1

General


Environmental Specifications

The following table lists the environmental specifications that general ly
apply to the ADAM-5000 system (System kernel and I/O modules).

Specification

Rating

Storage temperature

-13 to 185°F (-25 to 85°C)

Ambient operating
temperature

14 to 158°F (-10 to 70°C)

Ambient humidity*

5 to 95%, non-condensing

Atmosphere

No corrosive gases


* Equipment will operate below 30% humidity. However, static
electricity problems occur much more frequently at lower humidity
levels. Make sure you take adequate precautions before you touch
the equipment. Consider using ground straps, antistatic floor
cover- ings, etc. if you use the equipment in low humidity
environments.

Power Requirements

Although the ADAM-5000 systems are designed for standard
industrial unregulated 24 V

DC

power supply, they accept any power unit

that supplies within the range of +10 to +30V

DC

. The power supply

ripple must be limited to 100 mV peak-to-peak, and the immediate ripple
voltage should be maintained between +10 and +30 V

DC

.

Diagnostic Indicators

Diagnostic indicators are located on the front panel of the ADAM
system. They show both normal operation and system status in your
remote I/O system. The indicators are:

• System status (PWR, RUN)

• Communication status (TX, RX)

• I/O module status


2-2 ADAM-5000