Chapter 6

$aaSiCjAhEs

Example

command: $03S0C1ALEE(cr)

response: !03(cr)

Channel 1 of slot 0 in the ADAM-5000 system at
address 03h is instructed to enable its Low alarm
function.

The module confirms that its Low alarm function has
been enabled.

Note:

An analog input module requires a maximum of 2

seconds after it receives an Enable/Disable Alarm
command to let the setting take effect. During this
interval, the module cannot be addressed to perform
any other actions.