Command Set 5024 Analog Output

$aaSiCjArrff

Response !aa(cr) if the command is valid.

?aa(cr) if an invalid operation was entered.

There is no response if the module detects a syntax
error or communication error or if the specified address
does not exist.

! delimiter character indicating a valid command was
received.

? delimiter character indicating the command was
invalid.

aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.

(cr) is the terminating character, carriage return (0Dh)

Example

command: $35S3C0A3110(cr)

response: !35(cr)

The analog output channel 0 in slot 3 of the ADAM-
5000 system at address 35h is configured to an output
range 4 to 20mA, engineering units data format, and a
slew rate of 1.0mA/sec.

The response indicates that the command has been
received.

Note:

An analog output module requires a maximum of 20
milliseconds to perform auto calibration and ranging
after it is reconfigured. During this time span, the
module cannot be address to perform any other
actions.




6-92