Data Formats and I/O Ranges
B.2 Analog Input Ranges - ADAM-5018
Module
Range
Code
Input
Range
Description
Data
Formats
+F.S. Zero -F.S.
Displayed
Resolution
Actual
Value
Engineering
Units
+15.000
±00.000
-15.000
1 µV
% of FSR
+100.00
±000.00
-100.00
0.01%
00h ±15
mV
Two's
Complement
7FFF 0000 8000 1
LSB
Reading/
1000
Engineering
Units
+50.000
±00.000
-50.000
1 µV
% of FSR
+100.00
±000.00
-100.00
0.01%
01h ±50
mV
Two's
Complement
7FFF 0000 8000 1
LSB
Reading/
100
Engineering
Units
+100.00 ±000.00 -100.00 10
µV
%
of
FSR +100.00 ±000.00 -100.00 0.01%
02h ±100
mV
Two's
Complement
7FFF
0000
8000
1 LSB
Reading/
100
Engineering
Units
+500.00 ±000.00 -500.00 10
µV
%
of
FSR +100.00 ±000.00 -100.00 0.01%
03h ±500
mV
Two's
Complement
7FFF
0000
8000
1 LSB
Reading/
10
Engineering
Units
+1.0000 ±0.0000 -1.0000 100
µV
%
of
FSR +100.00 ±000.00 -100.00 0.01%
04h ±1
V
Two's
Complement
7FFF
0000
8000
1 LSB
Reading/
10000
Engineering
Units
+2.5000 ±0.0000 -2.5000 100
µV
%
of
FSR +100.00 ±000.00 -100.00 0.01%
05h ±2.5
V
Two's
Complement
7FFF
0000
8000
1 LSB
Reading/
10000
Engineering
Units
+20.000 ±00.000 -20.000 1
µA
%
of
FSR +100.00 ±000.00 -100.00 0.01%
06h ±20
mA
Two's
Complement
7FFF
0000
8000
1 LSB
Reading/
1000
ADAM-5018
07h Not
Used
B-4