Command Set Analog Input Alarm

5013/5017/5017H/5017UH/5018/5018P

$aaSiCjRhU

Name

Read Alarm Limit

Description Returns the High/Low alarm limit value for the specified

input channel in the addressed ADAM-5000 system

Syntax $aaSiCjRhU(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.

SiCj identifies the desired slot i (i : 0 to 3) and the
desired analog input channel j (j : 0 to 7).

RhU is the Read Alarm Limit command.

h indicates alarm type and can have the value H = High
alarm, L = Low alarm

(cr) represents terminating character, carriage return
(0Dh)

Response !aa(data)(cr)

if the command was valid

There is no response if the system detects a syntax error
or communication error or if the specified address does
not exist.

! delimiter character indicating a valid command was
received.

aa represents the 2-character hexadecimal address of the
corresponding ADAM-5000 system.

(data) represents the desired alarm limit setting. The
format is always in engineering units.

(cr) represents terminating character, carriage return
(0Dh)

6-86