beautypg.com

Command set – Advantech 5000 Series User Manual

Page 173

background image

Command Set

5050/5051/5052/5055/5056

5060/5068/5069 Digital I/O

$aaSi6

Name

Digital Data In

Description This command requests that the specified module in an

ADAM-5000 system at address aa return the status
of its digital input channels and a read back value of its
digital output channels.

Syntax

$aaSi6(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system.

Si identifies the I/O slot of the system you want to read.

6 is the Digital Data In command.

(cr) is the terminating character, carriage return (0Dh)
Response !aa(datainput)(datainput)00(cr)

if the

command is valid.

(ADAM-5051)

!aa(datainput)(dataoutput)00(cr) if the command is valid.

(ADAM-5055S)

!aa(dataoutput)(dataoutput)00(cr) if the command is
valid.

(ADAM-5056)

!aa(dataoutput)0000(cr) if the command is valid.

(ADAM-5060, ADAM-5068, ADAM-5069)

?aa(cr) if an invalid operation was entered.






6-108







ADAM-5000