beautypg.com

Command set 5024 analog output – Advantech 5000 Series User Manual

Page 169

background image

Command Set 5024 Analog Output

$aaSiCj3hh

(cr) is the terminating character, carriage return (0Dh)

Example

command: $07S1C2314(cr)

response: !07(cr)

The command tells channel 2 of the analog output
module in slot 1 of the ADAM-5000 system at address
07h to increase its output value by 20 (14h) counts
which is approximately 30 µA.

The analog output module confirms the increase.

Note:

In order to perform a Trim Calibration, either a mA
meter or a resistor and voltmeter should be connect-
ed to the module's output prior to calibration. (See
also the 4 mA and 20 mA Calibration commands of
the analog output module's command set. Refer also
to Chapter 4, Section 4.5, Analog Output Calibration for
a detailed description.)






















6-104

ADAM-5000