5 provisioning analog alarms – Alpha Technologies PowerAgent SC3 User Manual
Page 49

PowerAgent
TM
SC3 Site Controller
Document # 700-000014-01 Rev 2
Installation and Operation
Phoenix Broadband Technologies, LLC
10/28/2010
Page 49 of 57
6.5.5
Provisioning Analog Alarms
When the A button next to a measured parameter is pressed the Analog Alarm Setup screen 
shown below will appear. There are 4 Alarm Limits that can be set independently and an Alarm 
Enable check box for each alarm limit. When the enable box is checked, the alarm will occur 
when the Present Value crosses the Alarm Limit. In the example below there is a Minor Alarm 
because the Present Value is below the Minor Low Alarm Limit. 
 
The Deadband 
setting provides 
hysteresis so the 
alarm does not chatter 
if the Present Value 
is right at the alarm 
limit. For High alarms 
the alarm will occur 
when the present 
Value is greater than 
the Alarm Limit. The 
alarm will clear when 
the Present Value is 
less than the High 
Alarm Limit minus 
the Deadband. 
Likewise for a Low 
alarms, the alarm will 
occur when the 
present Value is less 
than the Alarm Limit. 
The alarm will clear 
when the Present 
Value is greater than 
the Low Alarm Limit 
plus the Deadband. 
 
Minor and major 
alarms operate independently so as the Present Value moves a minor alarm will become a major 
alarm and vise versa. 
 
Values in Yellow indicate a Minor alarm, Red indicates a Major alarm, and normal values are 
block. 
 
All alarm settings are nonvolatile and will be saved in the Site Controller database. 
 
SNMP Traps and/or Emails may be sent whenever the alarm state changes and when the alarm 
returns to the normal state. Refer to the Telnet Setup section of this manual for information on 
setting the Trap destinations and Email addresses. 
 
 
