difference between the Cell Admittance and the Initial Cell Admittance. To provision the
alarms press the A button next to the Cell Admittance Change field.

To set a baseline based on the present admittance reading press either the This Jar Only button
or the Entire String button in the Copy Cell Admittance to Initial Cell Admittance box. The
Present Admittance Cell Admittance value will be copied to the Initial Cell Admittance value and
the Cell Admittance Change field in the Single Jar Display will be updated to show the
difference between the Cell Admittance and the Initial Cell Admittance.