Alpha Technologies PowerAgent SC3 User Manual

Page 36

background image

PowerAgent

TM

SC3 Site Controller

Document # 700-000014-01 Rev 2

Installation and Operation

Phoenix Broadband Technologies, LLC

10/28/2010

Page 36 of 57


If the battery sensor is
equipped with the
electrolyte level
detection option the
Electrolyte Level will
be displayed as either
“Normal” or “Low”. If
the sensor is not
equipped with this
option the Electrolyte
Level
will not be
displayed.

For High Voltage
sensors only the
Sensor Address is
shown for sensor
identification.



The Sensor Status
provides an indication
of what is happening
at the sensor. The
table below lists the
possible values of the
Sensor Status.


Sensor Status

Description

Normal

This sensor is operating normally

Fault

There is no communications with this sensor

Measuring

This sensor is making an admittance measurement

SensorDisabled

This sensor was disabled through SNMP

StringDisabled

This string was disabled through SNMP

Missing

This sensor was expected based on the string voltage, but is not present

MeasurementFailed The last admittance measurement failed

Admittance measurements are normally made at a rate set by the Admittance Measurement
Interval
set in the Site Setup Display. Pressing the Measure Now button will initiate an
admittance measurement on this sensor the next time it is polled. The measurement may take a
minute to start depending on what the Site Controller is doing at the time. When the
measurement starts the Sensor Status will indicate “Measuring”. The status will return to normal
when the measurement is complete.

Pressing the Flash LED button commands the battery sensor to flash its LED alternating
between Red and Green. The Sensor LED Control indicator displays the state of the LED either
“Normal” or “Flash Green/Red”. Additional LED states can be set by the SNMP Manager. The
flashing LED can help onsite personnel locate a jar in a large deployment. Depending on what
the Site Controller is doing it may take a minute for the LED to start or stop flashing when the
button is pressed.