7 restore factory defaults (7), 8 exit (8), 9 save and exit (9) – Alpha Technologies PowerAgent SC3 User Manual
Page 29: 10 erase all string and jar data (13), 11 reset all sensors (14), 12 erase string (15), 13 erase rim/rom flash (16)

PowerAgent
TM
SC3 Site Controller
Document # 700-000014-01 Rev 2
Installation and Operation
Phoenix Broadband Technologies, LLC
10/28/2010
Page 29 of 57
5.9.7
Restore Factory Defaults (7)
To restore the factory default settings type a 7. All SNMP, Email, NTP, and HMS values will be
set to the factory defaults. The IP Address will not be changed, however the Gateway and Net
Mask settings will be set to the factory default values.
NOTE: Be careful. Changing the Gateway and Net Mask settings could prevent
communications with the Site Controller, requiring a site visit.
5.9.8
Exit (8)
Type a “8” followed by an “Enter”, to exit the setup program, close the telnet window without
saving the changes to nonvolatile memory, and without resetting the Site Controller. Some
changes will take affect (SNMP) others will not (Email).
5.9.9
Save and Exit (9)
Type a “9” followed by an “Enter”, to save all changes to nonvolatile memory, close the telnet
window, exit the setup program, and reset the Site Controller so all changes take affect.
5.9.10
Erase All String and Jar Data (13)
Typing “13” followed by “Enter” will erase all of the String and Jar data from the Site Controller
nonvolatile memory and then reset the Site Controller. All user entered data for the strings and
jars including names and alarm setups will be lost. The other settings will not be changed.
5.9.11
Reset All Sensors (14)
Typing “14” followed by “Enter” will reset all the Sensors. The telnet session will remain open and
no settings will be changed. The reset will force all of the sensors to be rediscovered.
5.9.12
Erase String (15)
Typing “15” followed by “Enter” will erase a specified string. You will be prompted for the string
number. The telnet session will remain open and no settings will be changed.
5.9.13
Erase RIM/ROM Flash (16)
Typing “16” followed by “Enter” will erase the RIM and ROM database. All settings will be lost
and the devices will no longer appear in the Web page or SNMP MIBs unless they are
rediscovered. The telnet session will close and the Site Controller will reset.