MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU)
COMMUNICATIONS GUIDE
Bit 25
S1 Disconnected
Bit 26
S2 Disconnected
Bit 27
S1 Connected
Bit 28
S2 Connected
Bit 29
Freqs Differ > 0.2Hz
Bit 30
Test Initiated
Bit 31
R15 / Disconnect from S2
FC183
32 bits
Fault Status 1
Bit 0
Any Fault
Bit 17
Comm Fail Fault
Bit 18
Relay Not Configured
Bit 19
Process ILock A Fault
Bit 20
Process ILock B Fault
Bit 21
Process ILock C Fault
Bit 22
Process ILock D Fault
Bit 23
Process ILock E Fault
Bit 24
Process ILock F Fault
Bit 25
Process ILock G Fault
Bit 26
Process ILock H Fault
Bit 27
Process ILock I Fault
Bit 28
Process ILock J Fault
FC184
32 bits
Fault Status 2
Bit 13
S1 & S2 Fail to Open
Bit 14
Phase Rotation Error
Bit 15
Sources Out of Phase
Bit 16
S1 Lmt Sw Not Closed
Bit 17
S1 Lmt Sw Not Opened
Bit 18
S2 Lmt Sw Not Closed
Bit 19
S2 Lmt Sw Not Opened
Bit 20
S1 Del Lmt Sw Not Closed
Bit 21
S1 Del Lmt Sw Not Opened
Bit 22
S2 Del Lmt Sw Not Closed
Bit 23
S2 Del Lmt Sw Not Opened
FC185
32 bits
Fault Status 3
Bit 8
ATS Lockout
Bit 9
S1 Failure to Disconnect
Bit 10
S2 Failure to Disconnect
Bit 11
S1 Failure to Connect
Bit 12
S2 Failure to Connect
Bit 13
S1 & S2 Fail to Disconnect
Bit 14
Phase Rotation Error
Bit 15
Sources Out of Phase
Bit 16
S1 Lmt Sw Not Closed
Bit 17
S1 Lmt Sw Not Opened
Bit 18
S2 Lmt Sw Not Closed
Bit 19
S2 Lmt Sw Not Opened
Bit 20
S1 Del Lmt Sw Not Closed
Code
Type
Definition