GE Industrial Solutions MX350 Communications Guide User Manual
Page 55

COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU)
MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE
51
0xBA02
S2 Underfrequency
0xBA42
S2 Overfrequency
0xBA82
S1 Volt Imbalance Alarm
0xBAC2
S2 Volt Imbalance Alarm
0xBB02
Inhibited via Disconnect Switch
0xBB42
Switch Exercising
0xBB82
Neutral Position
0xBBC2
Xfer to Alternate Source
0xBC02
S1 to S2 Auto Xfer Alert
0xBC42
S2 to S1 Auto Xfer Alert
0xBC82
S1 to S2 Inhibit
0xBCC2
S2 to S1 Inhibit
0xBD02
Engine Start
0xBD42
Auto Load Shed Active
0xBD82
Not in Auto
0xBDC2
S1 Failure
0xBE02
Alternate Source Fail to Start
0xBEC2
S1 Connected
0xBF02
S2 Connected
0xBE42
S1 Disconnected
0xBE82
S2 Disconnected
0xBF42
Freqs Differ > 0.2Hz
0xBF82
Test Initiated
0xC802
Access Switch Closed
0xD802
S2 Sol Relay
0xD842
S2 Sol Delay Relay
0xD882
S1 Sol Relay
0xD8C2
S1 Sol Delay Relay
0xD902
Engine Start Signal (Open=ON)
0xD942
Bypass ATS On S2
0xD982
Bypass ATS On S1
0xDA42
Load Control 1
0xDA82
Load Control 2
0xDAC2
Load Control 3
0xDB02
Load Control 4
0xDB42
Load Control 5
0xDB82
Load Control 6
0xDBC2
S2 Set as Pref Source
0xDC02
S1 CB Fail to Close
0xDC42
S2 CB Fail to Close
0xDC82
Remove S1 from MX350
0xDCC2
Remove S2 from MX350
0xDD02
S1 CB Closed
0xDD42
S1 CB Open
0xDD82
S1 CB Relay Lockout
Code
Type
Definition