COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU)
MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE
39
43172
0C63
Auto Mode Shed kW Bypass
0
1
1
---
FC126
0
1
43173
0C64
Reserved
---
---
---
---
---
---
1
to
to
Reserved
---
---
---
---
---
---
1
43178
0C69
Reserved
---
---
---
---
---
---
1
ATS CONTROL TIMERS
43179
0C6A
Time Delay to Preferred Source 0
600
1
---
F24
5
1
43180
0C6B
Time Delay to Alternate Source 0
600
1
---
F24
5
1
43181
0C6C
Gen Run Timer Value
0
3600
1
---
F24
0
1
43182
0C6D
Time Delay for Gen Sag
0
30
1
---
F24
0
1
43183
0C6E
Delay for Generator Start
0
15541
1
---
F24
3
1
43184
0C6F
S2 Failure Response Delay (P2) 0
15540
1
---
F24
3
1
43185
0C70
Time Delay to Preferred Source 0
15540
1
---
F24
1800
1
43186
0C71
Reserved
---
---
---
---
---
---
1
43187
0C72
Delay for Engine Cooldown
0
3600
1
---
F24
300
1
43188
0C73
U2 Timer Value
0
3600
1
---
F24
600
1
43189
0C74
Time Delay to Alternate Source 0
15540
1
---
F24
3
1
43190
0C75
Pre Load Control 1 (LC1) Timer 0
3600
1
---
F24
0
1
43191
0C76
Pre Load Control 2 (LC2) Timer 0
3600
1
---
F24
0
1
43192
0C77
Pre Load Control 3 (LC3) Timer 0
3600
1
---
F24
0
1
43193
0C78
Pre Load Control 4 (LC4) Timer 0
3600
1
---
F24
0
1
43194
0C79
Pre Load Control 5 (LC5) Timer 0
3600
1
---
F24
0
1
43195
0C7A
Pre Load Control 6 (LC6) Timer 0
3600
1
---
F24
0
1
43196
0C7B
Post Load Control 1 (LC1) Timer 0
3600
1
---
F24
0
1
43197
0C7C
Post Load Control 2 (LC2) Timer 0
3600
1
---
F24
0
1
43198
0C7D
Post Load Control 3 (LC3) Timer 0
3600
1
---
F24
0
1
43199
0C7E
Post Load Control 4 (LC4) Timer 0
3600
1
---
F24
0
1
43200
0C7F
Post Load Control 5 (LC5) Timer 0
3600
1
---
F24
0
1
43201
0C80
Post Load Control 6 (LC6) Timer 0
3600
1
---
F24
0
1
43202
0C81
Reserved
---
---
---
---
---
---
1
to
to
Reserved
---
---
---
---
---
---
1
43207
0C86
Reserved
---
---
---
---
---
---
1
ATS R50
43208
0C87
Max Frequency Difference
0
500
1
Hz
F3
500
1
43209
0C88
Sync Phase Angle Limit
0
21
1
°
F1*
10
1
43210
0C89
Reserved
---
---
---
---
---
---
1
to
to
Reserved
---
---
---
---
---
---
1
43233
0CA0
Reserved
---
---
---
---
---
---
1
ATS SOURCE 1 CONFIGURATION
43234
0CA1
S1 Overfreq Fail
501
631
1
Hz
F2*
631
1
43235
0CA2
S1 Overfreq Restore
500
629
1
Hz
F2
629
1
43236
0CA3
S1 Overvolt Fail
105
111
1
%
F1*
110
1
43237
0CA4
S1 Overvolt Restore
103
108
1
%
F1
105
1
43238
0CA5
S1 Underfreq Fail
450
599
1
Hz
F2
590
1
43239
0CA6
S1 Underfreq Restore
451
600
1
Hz
F2
595
1
43240
0CA7
S1 Undervolt Fail
75
99
1
%
F1
80
1
43241
0CA8
S1 Undervolt Restore
85
100
1
%
F1
90
1
Modbus
Hex
Description
Min
Max
Step
Units
Format Default
Size in
Words