6
MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU)
COMMUNICATIONS GUIDE
Function Code 03H
Modbus implementation: Read Holding Registers
MX350 implementation: Read Setpoints
For the MX350 implementation of Modbus, this function code can be used to read any
setpoints (“holding registers”). Holding registers are 16 bit (two byte) values transmitted
high order byte first. Thus all MX350Setpoints are sent as two bytes. The maximum
number of registers that can be read in one transmission is 125.
The slave response to this function code is the slave address, function code, a count of the
number of data bytes to follow, the data itself and the CRC. Each data item is sent as a two
byte number with the high order byte sent first.
For example, consider a request for slave 17 to respond with 3 registers starting at address
006B. For this example the register data in these addresses is as follows:
Command Number
Description
196
Reset Time S2 Available Counter
197
Alarm Silence
198
Control to bypass W-timer
199
Control to bypass T-timer
200
Net Ctrl Test on No load
201
Fast Load Test Control
202
Regular Load Test Control
203
Auto/Manual retransfer to S1
204
Auto/Manual transfer to S1/S2
205
Net Ctrl Load Shed for S1
206
Net Ctrl Inhibit Transfer to S2
207
Net Ctrl Inhibit Transfer to S1
208
Net Ctrl Transition Mode Selector
209
Command to Bypass R50
210
Confirm Bypass R50
211
Cancel Bypass R50
212
Bypass Pending Exerciser
213
Cancel Exerciser Bypass
214
Net Ctrl Auto Transfer Inhibit
215
Net Ctrl Auto Transfer Relay
216
Net Ctrl Bypass Active ATS Timer
217
Net Ctrl Exerciser Cancel
218
Net Ctrl Generator Start
219
Net Ctrl Generator Stop
220
Net Ctrl Load Shed for S2
221
Net Ctrl Prime Source Selection
222
Net Ctrl Test Mode Cancel
223
Net Ctrl Test On Load
224
Net Ctrl Transfer Commit
Address
Data
006B
022B
006C
0000
006D
0064