18
MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU)
COMMUNICATIONS GUIDE
30668
029B
Ia
---
---
---
A
F10
N/A
2
30670
029D
Ib
---
---
---
A
F10
N/A
2
30672
029F
Ic
---
---
---
A
F10
N/A
2
30674
02A1
In State
---
---
---
---
FC200
N/A
1
30675
02A2
Iunb
---
---
---
%
F1
N/A
1
30676
02A3
Ig
---
---
---
A
F10
N/A
2
30678
02A5
Vab
---
---
---
V
F1
N/A
1
30679
02A6
Vbc
---
---
---
V
F1
N/A
1
30680
02A7
Vca
---
---
---
V
F1
N/A
1
30681
02A8
Van
---
---
---
V
F1
N/A
1
30682
02A9
Vbn
---
---
---
V
F1
N/A
1
30683
02AA
Vcn
---
---
---
V
F1
N/A
1
30684
02AB
Freq
---
---
---
Hz
F3
N/A
1
30685
02AC
Power Factor
---
---
---
---
F21
N/A
1
30686
02AD
Real Power
---
---
---
kW
F13
N/A
2
30688
02AF
Reactive Power
---
---
---
kvar
F13
N/A
2
30690
02B1
Apparent Power
---
---
---
kVA
F2
N/A
1
30691
02B2
Reserved
---
---
---
---
---
---
1
to
to
Reserved
---
---
---
---
---
---
1
30709
02C4
Reserved
---
---
---
---
---
---
1
TRACE MEMORY
30710
02C5
Trigger Date
---
---
---
---
F18
N/A
2
30712
02C7
Trigger Time
---
---
---
---
F19
N/A
2
30714
02C9
Trigger Cause
---
---
---
---
FC133
N/A
1
30715
02CA
Trigger Frequency
---
---
---
Hz
F3
N/A
1
30716
02CB
Total Triggers
---
---
---
---
F1
N/A
1
30717
02CC
Reserved
---
---
---
---
---
---
1
30718
02CD
Trigger Position
---
---
---
---
F1
N/A
1
30719
02CE
Trace Memory Start Index
---
---
---
---
F1
N/A
1
TRACE MEMORY SAMPLES
30720
02CF
Sample Index + Trace Memory
Sample 1
---
---
---
---
F4
N/A
1
30721
02D0
Sample Index + Trace Memory
Sample 2
---
---
---
---
F4
N/A
1
30722
02D1
Sample Index + Trace Memory
Sample 3
---
---
---
---
F4
N/A
1
30723
02D2
Sample Index + Trace Memory
Sample 4
---
---
---
---
F4
N/A
1
to
to
Reserved
---
---
---
---
---
---
1
30844
034B
Sample Index + Trace Memory
Sample 125
---
---
---
---
F4
N/A
1
30845
034C
Sample Index + Trace Memory
Sample 126
---
---
---
---
F4
N/A
1
30846
034D
Sample Index + Trace Memory
Sample 127
---
---
---
---
F4
N/A
1
30847
034E
Sample Index + Trace Memory
Sample 128
---
---
---
---
F4
N/A
1
30848
034F
Reserved
---
---
---
---
---
---
1
to
to
Reserved
---
---
---
---
---
---
1
Modbus
Hex
Description
Min
Max
Step
Units
Format Default
Size in