Assembly

49

PNEG-720-G2 12" & 16" Series II Sweep

C. Locking the Amp Meter

1. Locking the amp meter is not required, but does prevent the meter from being tampered with

once it is programmed.

2. In RUN MODE press "LOCK" three (3) times within five (5) seconds.

This value = A number that is easily remembered.
Use arrow buttons to change value.
a. Press "ENTER".

D. Unlocking the Amp Meter

1. In RUN MODE press "LOCK" three (3) times within five (5) seconds.

a. Enter the "LoC" value.

Use arrow buttons to change value.

b. Press "ENTER".

18 . CONTROL PANEL SETUP (CONT.)

It is recommended to write down the "LoC" value and keep it in a safe place in
case it is forgotten.

f.

Press "Enter"
Value = 50
Use arrow buttons to change value.

g. Press "ENTER" to "LoCut".

This value = 0

h. Press "ENTER" to RUN MODE.

3. Setting Presets

a. Press "Pre A".
b. Press "PRGM"

This value = "High Amp Set Point".
Use arrow buttons to change value.

c. Press "ENTER".

4. Setting Relays

a. Press "PRGM" to "rELAYS".
b. Press "ENTER" to "HYS A".
c. Press "PRGM"

This value = "High Amp Set Point" - "Low Amp Set Point"
Use arrow buttons to change value.

d. Press "ENTER" to RUN MODE.

EXAMPLE:

Full Load Running Amps = 21 Amps
High Amp Set Point = 20 Amps
Low Amp Set Point = 12 Amps

Then "HYS A" = 8 Amps (NOTE: This is the difference between the High Amp Set Point
and the Low Amp Set Point. [20 Amps - 12 Amps = 8 Amps])
And "Pre A" = 20 Amps