B. Pin Assignments and Indicators

System Alarm
Connection
Requirements

The CPX-1000 includes an Alarm board in the summary alarm
panel at the top of the shelf. This Alarm board continuously
monitors various internal system operating parameters and
reports alarms (if failures are detected). Dry Form-A closures

1

are

provided for critical, major, and minor alarm connections to
external local alarm surveillance equipment.

The closure specifications are:

Rated resistive load: 20 Ohms (typical) @ 50 mA, 5 Ohms
(typical) @ 100 mA

Rated inductive load: not applicable

Operating voltage: 100 VDC/VAC (350 VDC or peak ac for
100 ms transients)

Continuous load: 250 mA dc, 150 mA ac

Minimum load: 10

µA at 10mVDC

Critical alarm closure is normally closed. Major and minor closures
are normally open.

1. Optically coupled, CMOS FET bipolar switches

Table B–5. Remote Alarm Connector Pin Assignments

Pin

Signal

1

Critical Alarm

2

Critical Alarm Return

3

Major Alarm

4

Major Alarm Return

5

Minor Alarm

6

Minor Alarm Return

7

Rack Alarm (not used)

8

Rack Alarm Return (not used)