Ups subsystem errors, Ups subsystem errors 22, Table a-3 – Sun Microsystems SUN STOREDGETM 5310 NAS User Manual
Page 40: Ups error
1-22
Sun StorEdge 5310 NAS Troubleshooting Guide • December 2004
UPS Subsystem Errors
Refer to Table A-3 for descriptions of UPS error conditions.
TABLE A-3
UPS Error Messages
Event
E-Mail Subject: Text
SNMP Trap
LCD Panel
Log
Power Failure
AC Power Failure:
AC power failure. System is running
on UPS battery.
Action: Restore system power.
Severity = Error
EnvUpsOn
Battery
U20 on
battery
UPS: AC power
failure. System is
running on UPS
battery.
Power Restored
AC power restored:
AC power restored. System is running
on AC power.
Severity = Notice
EnvUpsOff
Battery
U21 power
restored
UPS: AC power
restored.
Low Battery
UPS battery low:
UPS battery is low. The system will
shut down if AC power is not restored
soon.
Action: Restore AC power as soon as
possible.
Severity = Critical
EnvUpsLow
Battery
U22 low
battery
UPS: Low battery
condition.
Normal Battery
UPS battery recharged:
The UPS battery has been recharged.
Severity = Notice
EnvUps
Normal
Battery
U22 battery
normal
UPS: Battery
recharged to
normal condition.
Replace Battery
Replace UPS Battery:
The UPS battery is faulty.
Action: Replace the battery.
Severity = Notice
EnvUps
Replace
Battery
U23 battery
fault
UPS: Battery
requires
replacement.
UPS Alarms -
Ambient
temperature or
humidity
outside
acceptable
thresholds
UPS abnormal temperature/humidity:
Abnormal temperature/humidity
detected in the system.
Action: 1. Check UPS unit installation,
OR
2. Contact technical support.
Severity = Error
EnvUps
Abnormal
U24
abnormal
ambient
UPS: Abnormal
temperature
and/or humidity
detected.