beautypg.com

As-interface slaves, I/o modules for operation in ip20 control cabinet – Siemens ISI EN 50295 User Manual

Page 91

background image

Siemens IK PI · 2004

6/91

AS-Interface Slaves

I/O modules for operation in IP20 control cabinet

Module F90

6

Technical specifications (continued)

16 inputs

Screw-type terminals

Combicon connection

Transistor PNP
3RG9 002-0DE00

3RG9 004-0DE00

Slave type

Standard slaves

Operational voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Total current input in mA

£ 70

Input connection

PNP

Inputs

• Sensor supply via AS-Interface

Short-circuit and overload proof

• Voltage range in V

20 to 30

• Connection of sensors

Mechanical contacts

• Signal 1 U

in

20 to 30 V

³ 3 mA

Group signal

• Current carrying capacity Iout

£ 25 mA

• Output voltage U

out

20 to 30 V

Watchdog

Built-in

I/O configuration

7

ID/ID2 code

F/F

Assignment of data bits

• Data bit D0

Group signal G1 (D0)
Inputs I 1.1 to I 1.4 (D0 to D3)

• Data bit D1

Group signal G2 (D1)
Inputs I 2.1 to I 2.4 (D0 to D3)

• Data bit D2

Group signal G3 (D2)
Inputs I 3.1 to I 3.4 (D0 to D3)

• Data bit D3

Group signal G4 (D3)
Inputs I 4.1 to I 4.4 (D0 to D3)

AS-Interface certificate

Yes

Approvals

UL, CSA, ship building

Degree of protection

IP20

Ambient temperature in °C

-25 to +70

Storage temperature in °C

-40 to +85

Displays

• Inputs/outputs

Yellow LED

Connection

Via screw terminal

Via Combicon pin connector

Addressing

An integrated addressing socket can be used

Note 1

The module has four input groups. Each input group has four inputs and one group signal for power supply
of the inputs. The input groups are activated separately, whereby the relevant group signal is set by the control.
Then the switching states of the associated inputs are read in.

Note 2

Function block required

Note 3

To supply the output circuit, an external supplementary supply (AUX POWER) of 20 to 30 V DC is necessary.
The supplementary supply must comply with VDE 0106 (PELV), safety class III.