beautypg.com

Power supply units ip20, As-interface power supply units – Siemens ISI EN 50295 User Manual

Page 136

background image

Siemens IK PI · 2004

6/136

AS-Interface Power Supply Units

Power supply units IP20

6

Technical specifications

AS-Interface power supply unit

Single output IP20
Output current 2.4 A

Output current 4 A

Output current 3.3 A

3RX9 307-0AA00

3RX9 307-1AA00

4FD5 213-0AA10-1A

Rated input voltage in V

115/230 AC

115/230 AC

230/400 AC

Input

Single-phase AC

Single-phase AC

Single- and two-phase AC

• Range selection

With changeover switch

With plug

• Voltage range in V

195 to 253 / 102 to 132 AC

197 to 430 AC

• Overvoltage strength

EN 61 000-4-1

• Mains buffering at

,

e

Rated in ms

> 20

> 20 at 230 V; > 60 at 400 V

• Mains frequency rated value I

range in Hz

50/60/47 to 63

• Built-in input fuse in A

T 2

T 5 (not accessible)

T 3 (not accessible)

• Recommended m.c.b (IEC898)

in mains supply circuit in A

From 10, characteristic C

From 10, characteristic C

From 16, characteristic C

Output

• Stabilized floating DC voltage acc.

to AS-Interface specification

Yes

Yes, can be connected in parallel

• Voltage rating U

aRated

in V

30 DC

• Total tolerance in V

29.5 to 31.6 DC

• Residual ripple in mVpp

(0–10 kHz, AS-i+/AS-i–)

< 300

• Spikes in mVpp

(10–500 kHz, AS-i+/AS-i–)

< 50

• Operational display

Green LED

• Current rating

,

a Rated

in A

2.4 (power boost: 2.8)

4 (power boost: 4.5)

DC 3.3 (power boost: DC 4)

Efficiency/power loss

• Efficiency at U

aRated

,

,

aRated

in %

Approx. 85

• Power loss at U

aRated

,

,

aRated

in W Approx. 10

Approx. 18

Approx. 15

Protective and monitoring functions

• Output overvoltage protection

No

• Current limitation in A

> 2.8

> 5

• Short-circuit protection

Yes

Safety

• Primary/secondary isolation

SELV to EN 60 950

SELV to EN 60 950 (in preparation)

SELV to EN 60 950

• Safety class (EN 60 950/IEC 950)

I

• Degree of protection

IP20

• Approvals

CE, UL, marine

CE, UL, CSA (in preparation)

CE, UL (in preparation)

EMC

• Emitted interference

EN 50 081-1

• Noise immunity

EN 50 082-2

Operational data

• Ambient temperature range in °C -25 to +55

-45 to +55

• Transport and storage

temperature range in °C

-25 to +60

-45 to +80

• Humidity class

Max. 80% rel. humidity

Mechanical data

• Input connection

Spring-loaded terminal connection (0.8 to 2.5 mm

2

)

• Output connection AS-i +

Spring-loaded terminal connection (0.8 to 2.5 mm

2

)

• Output connection AS-i -

Spring-loaded terminal connection (0.8 to 2.5 mm

2

)

• Output connection shield S

Spring-loaded terminal connection (0.8 to 2.5 mm

2

)

• Output connection Ground

-

-

Spring-loaded terminal connection
(0.8 to 2.5 mm

2

)

• Dimensions (W x H x D) in mm

46

´ 135 ´ 105

75

´ 135 ´ 107

75

´ 135 ´ 103

• Mounting

Snap-on mounting onto standard rail
DIN EN 50 022-35 x 7.5 mm

Mounting onto standard rail