Technical specifications
AS-Interface power supply unit
Single output IP20
Output current 2.4 A
Output current 4 A
Output current 3.3 A
3RX9 307-0AA00
3RX9 307-1AA00
4FD5 213-0AA10-1A
Rated input voltage in V
115/230 AC
115/230 AC
230/400 AC
Input
Single-phase AC
Single-phase AC
Single- and two-phase AC
• Range selection
With changeover switch
With plug
• Voltage range in V
195 to 253 / 102 to 132 AC
197 to 430 AC
• Overvoltage strength
EN 61 000-4-1
• Mains buffering at
,
e
Rated in ms
> 20
> 20 at 230 V; > 60 at 400 V
• Mains frequency rated value I
range in Hz
50/60/47 to 63
• Built-in input fuse in A
T 2
T 5 (not accessible)
T 3 (not accessible)
• Recommended m.c.b (IEC898)
in mains supply circuit in A
From 10, characteristic C
From 10, characteristic C
From 16, characteristic C
Output
• Stabilized floating DC voltage acc.
to AS-Interface specification
Yes
Yes, can be connected in parallel
• Voltage rating U
aRated
in V
30 DC
• Total tolerance in V
29.5 to 31.6 DC
• Residual ripple in mVpp
(0–10 kHz, AS-i+/AS-i–)
< 300
• Spikes in mVpp
(10–500 kHz, AS-i+/AS-i–)
< 50
• Operational display
Green LED
• Current rating
,
a Rated
in A
2.4 (power boost: 2.8)
4 (power boost: 4.5)
DC 3.3 (power boost: DC 4)
Efficiency/power loss
• Efficiency at U
aRated
,
,
aRated
in %
Approx. 85
• Power loss at U
aRated
,
,
aRated
in W Approx. 10
Approx. 18
Approx. 15
Protective and monitoring functions
• Output overvoltage protection
No
• Current limitation in A
> 2.8
> 5
• Short-circuit protection
Yes
Safety
• Primary/secondary isolation
SELV to EN 60 950
SELV to EN 60 950 (in preparation)
SELV to EN 60 950
• Safety class (EN 60 950/IEC 950)
I
• Degree of protection
IP20
• Approvals
CE, UL, marine
CE, UL, CSA (in preparation)
CE, UL (in preparation)
EMC
• Emitted interference
EN 50 081-1
• Noise immunity
EN 50 082-2
Operational data
• Ambient temperature range in °C -25 to +55
-45 to +55
• Transport and storage
temperature range in °C
-25 to +60
-45 to +80
• Humidity class
Max. 80% rel. humidity
Mechanical data
• Input connection
Spring-loaded terminal connection (0.8 to 2.5 mm
2
)
• Output connection AS-i +
Spring-loaded terminal connection (0.8 to 2.5 mm
2
)
• Output connection AS-i -
Spring-loaded terminal connection (0.8 to 2.5 mm
2
)
• Output connection shield S
Spring-loaded terminal connection (0.8 to 2.5 mm
2
)
• Output connection Ground
-
-
Spring-loaded terminal connection
(0.8 to 2.5 mm
2
)
• Dimensions (W x H x D) in mm
46
´ 135 ´ 105
75
´ 135 ´ 107
75
´ 135 ´ 103
• Mounting
Snap-on mounting onto standard rail
DIN EN 50 022-35 x 7.5 mm
Mounting onto standard rail