beautypg.com

As-interface slaves, I/o modules for operation in ip20 control cabinet – Siemens ISI EN 50295 User Manual

Page 89

background image

Siemens IK PI · 2004

6/89

AS-Interface Slaves

I/O modules for operation in IP20 control cabinet

Module F90

6

Technical specifications

4 inputs/4 outputs

1 A

2 A

1 A

2 A

screw-type terminals

Combicon connection

3RG9 002-0DB00

3RG9 002-0DA00

3RG9 004-0DB00

3RG9 004-0DA00

Slave type

Standard slaves

Operational voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Total current input in mA

£ 270

Input connection

PNP

Inputs

• Sensor supply via AS-Interface

Short-circuit and overload proof

• Voltage range in V

20 to 30

• Load rating for sensor supply in

mA

200

• Connection of sensors

2- and 3-wire system

• Switching level High in V

³ 10

• Input current Low/High in mA

£ 1.5 / ³ 5

Outputs

• Type of output

Electronics

• Current carrying capacity in A

DC 12 / DC 13 typ.

1

2

1

2

• Total current of all outputs in A

4

6

4

6

• Short-circuit protection

Built-in

• Inductive interference protection

(free-wheeling diode)

Built-in

• External voltage supply 24 V DC

Built-in via terminal screws

Built-in via Combicon male connector

Watchdog

Built-in

I/O configuration

7

ID/ID2 code

0/F

Assignment of data bits

• Data bit D0

IN1/OUT1

• Data bit D1

IN2/OUT2

• Data bit D2

IN3/OUT3

• Data bit D3

IN4/OUT4

AS-Interface certificate

Yes

Approvals

UL, CSA, ship building

Degree of protection

IP20

Ambient temperature in °C

-25 to +70

Storage temperature in °C

-40 to +85

Displays

• Inputs/outputs

Yellow LEDs

• AS-I voltage

Green LED

Connection

Via screw terminal

Via Combicon pin connector

Addressing

An integrated addressing socket can be used

Note

To supply the output circuit, an external supplementary supply (AUX POWER) of 20 to 30 V DC is necessary.
The supplementary supply must comply with VDE 0106 (PELV), safety class III.