As-interface slaves, I/o modules for operation in ip20 control cabinet – Siemens ISI EN 50295 User Manual
Page 89
Siemens IK PI · 2004
6/89
AS-Interface Slaves
I/O modules for operation in IP20 control cabinet
Module F90
6
■
Technical specifications
4 inputs/4 outputs
1 A
2 A
1 A
2 A
screw-type terminals
Combicon connection
3RG9 002-0DB00
3RG9 002-0DA00
3RG9 004-0DB00
3RG9 004-0DA00
Slave type
Standard slaves
Operational voltage in accordance
with AS-Interface specification in V
26.5 to 31.6
Total current input in mA
£ 270
Input connection
PNP
Inputs
• Sensor supply via AS-Interface
Short-circuit and overload proof
• Voltage range in V
20 to 30
• Load rating for sensor supply in
mA
200
• Connection of sensors
2- and 3-wire system
• Switching level High in V
³ 10
• Input current Low/High in mA
£ 1.5 / ³ 5
Outputs
• Type of output
Electronics
• Current carrying capacity in A
DC 12 / DC 13 typ.
1
2
1
2
• Total current of all outputs in A
4
6
4
6
• Short-circuit protection
Built-in
• Inductive interference protection
(free-wheeling diode)
Built-in
• External voltage supply 24 V DC
Built-in via terminal screws
Built-in via Combicon male connector
Watchdog
Built-in
I/O configuration
7
ID/ID2 code
0/F
Assignment of data bits
• Data bit D0
IN1/OUT1
• Data bit D1
IN2/OUT2
• Data bit D2
IN3/OUT3
• Data bit D3
IN4/OUT4
AS-Interface certificate
Yes
Approvals
UL, CSA, ship building
Degree of protection
IP20
Ambient temperature in °C
-25 to +70
Storage temperature in °C
-40 to +85
Displays
• Inputs/outputs
Yellow LEDs
• AS-I voltage
Green LED
Connection
Via screw terminal
Via Combicon pin connector
Addressing
An integrated addressing socket can be used
Note
To supply the output circuit, an external supplementary supply (AUX POWER) of 20 to 30 V DC is necessary.
The supplementary supply must comply with VDE 0106 (PELV), safety class III.