Siemens IK PI · 2004

6/147

AS-Interface

System components and accessories

Addressing units

6

Overview

Before data transfer can take place with the master, addresses
must be assigned to all stations before the AS-Interface network
is created. This can

• be performed offline using an addressing unit or

• online using a master of the AS-Interface system.

The addresses themselves are the values 1 to 31 (or 1A to 31A
and 1B to 31B for the extended specification). A new slave that
has not yet been addressed has the address 0. It is recognized,
also by the master, as a new slave (not yet addressed) and is not
integrated in the normal communication in this state.

The addresses are assigned as required, i.e. it is of no conse-
quence whether the first slave has the address 21 or whether ad-
dress 1 is assigned to the first slave.

Function

• Reading out the slave addresses 0 to 31, A/B

• Reading out the I/O and ID-codes of the slaves

• Standard and expanded ID-code 1 and ID-code 2

• Standard and expanded addressing mode according to

AS-Interface Version 2.1

• Programming ID-code 1

• Function testing of slaves: Read inputs and wire outputs of dig-

ital or anlog slaves

• AS-Interface test: Measurement of voltage (measuring range

0 to 35 V) and current consumption (measuring range 0 to
100 mA) of the AS-Interface bus

• Storage: Complete plant configurations can be saved (profiles

of all slaves, also extension in accordance with AS-Interface
specification 2.1)

• Detection of complete system configurations

Technical specifications

AS-Interface addressing and diagnostic unit
3RK1 904-2AB01

Power supply

The standard power supply is provided by 4 IEC LR6 (NEDA 15)
batteries and guarantees that at least 2,500 addressing operations
can be performed. To save the batteries, automatic switch-off takes
place approx. 1 min. after the last button operation.

Ambient conditions

• Operating temperature range in °C

0 to +55

• Storage temperature range in °C

-20 to +55 (without batteries)

• Relative humidity in %

Max. 75, condensation must be prevented

• Height above sea level in m

Up to 2,000

• Installation site

Indoors only

Mechanical design

• Degree of protection

- Units

IP50

- Connection sockets

IP20

• Dimensions in mm

84 x 195 x 35

• Connection

via M12 socket