beautypg.com

As-interface slaves, I/o modules for operation in the field, Digital i/o modules ip67 - k45 – Siemens ISI EN 50295 User Manual

Page 59

background image

Siemens IK PI · 2004

6/59

AS-Interface Slaves

I/O modules for operation in the field

Digital I/O modules IP67 - K45

6

Technical specifications (continued)

1) The typical current carrying capacity per output increases with Version "E12" from 1.5 to 2 A (available from approx. 07/2003).

2x2 inputs

2 inputs / 2 outputs

2 x (1 input / 1 output)

--

Current carrying capacity
of outputs: 2 A

1

)

Current carrying capacity
of outputs: 0.2 A

A/B slaves

Standard slave

Standard slaves

Y assignment

Standard assignment

Standard assignment

M12

M12

M12

3RK2 200–0CQ22–0AA3

3RK1 400–1BQ20–0AA3

3RK1 400–0GQ20–0AA3

Total current input in mA

£ 270

£ 270

£ 270

Polarity reversal protection U Aux

Not applicable

Through coding

U Aux not required

Socket assignment, inputs

PIN1 = Sensor supply L+
PIN3 = Sensor supply L-
PIN4 + 2 = Data input
PIN5 = Ground connection

PIN1 = Sensor supply L+
PIN2 = Data input
PIN3 = Sensor supply L
PIN4 = Data input
PIN5 = Earth connection

PIN1 = Sensor supply L+
PIN2 = Output
PIN3 = Sensor supply L-
PIN4 = Data input
PIN5 = Earth connection

Outputs

• Current carrying capacity per

output in A DC 12 / DC 13 typ.

--

2

1

)

0,2

• Maximum summation current

per module in A

--

3

0,2

I/O configuration

0

3

3

ID/ID2 code

A/0

0/F

F/F

Assignment of data bits

• Socket 1

PIN4 = IN1 (D0)
PIN2 = IN2 (D1)

PIN4/2 = IN1(D0)

PIN4 = IN1(D0)
PIN2 = OUT3(D2)

• Socket 2

--

PIN4/2 = IN2(D1)

--

• Socket 3

--

PIN4 = OUT3(D2)

--

• Socket 4

PIN4 = IN3 (D2)
PIN2 = IN4 (D3)

PIN4 = OUT4(D3)

PIN4 = IN2(D1)
PIN2 = OUT3(D3)

Number of I/O sockets

2

4

2

4 outputs

3 outputs

2 outputs / 2 inputs

Current carrying capacity
of outputs: 1 A

Current carrying capacity
of outputs: 1 A

Current carrying capacity
of outputs: 2 A

Standard slaves

A/B slaves

A/B slave

Standard assignment

Standard assignment

Standard assignment

M12

M12

M12

3RK1 100–1CQ20–0AA3

3RK2 100–1EQ20–0AA3

3RK2 400–1BQ20–0AA3

Total current input in mA

£ 45

£ 45

£ 270

Polarity reversal protection U Aux

Through coding

Through coding

Through coding

Socket assignment, inputs

--

--

PIN1 = Sensor supply L+
PIN2 = Data input
PIN3 = Sensor supply L
PIN4 = Data input
PIN5 = Earth connection

Outputs

• Current carrying capacity per out-

put in A DC 12 / DC 13 typ.

1

1

2

• Maximum summation current per

module in A

3

3

3

I/O configuration

8

8

B

ID/ID2 code

0/F

A/0

A/0

Assignment of data bits

• Socket 1

PIN4 = OUT1(D0)

PIN4 = OUT1(D0)

PIN4/2 = IN3(D2)

• Socket 2

PIN4 = OUT2(D1)

PIN4 = OUT2(D1)

PIN4/2 = IN4(D3)

• Socket 3

PIN4 = OUT3(D2)

PIN4 = OUT3(D2)

PIN4 = OUT1(D0)

• Socket 4

PIN4 = OUT4(D3)

Not available

PIN4 = OUT2(D1)

Number of I/O sockets

4

3

4