As-interface slaves, I/o modules for operation in ip20 control cabinet, Introduction – Siemens ISI EN 50295 User Manual
Page 76
Siemens IK PI · 2004
6/76
AS-Interface Slaves
Introduction
I/O modules for operation in IP20 control cabinet
6
■
Function
Addressing
All modules of the Slimline S22.5, S45 and F90 series as well as
the flat module can be addressed via an integrated addressing
socket also in the mounted state. An addressing unit is therefore
necessary (AS-Interface addressing and diagnostics unit 3RK1
904-2AB01).
LED diagnostics indication
SlimLine Series
AS-Interface modules of the SlimLine Series have, in addition to
status indicators for inputs and outputs, two LEDs for indicating
the status of the module.
1) No LED for 3RK1 400-0BE00-0AA2, 3RK1 402-0BE00-0AA2 and 3RK1 100-0CE00-0AA2.
F90 module (16I)
All modules of this series have, in addition to status indicators for
inputs and outputs, one LED to indicate the status of the AS-In-
terface voltage.
Flat module and F90 module (4I/4O)
The flat module and F90 module with four inputs and four out-
puts have a dual LED for diagnostics functions.
LED
AUX PWR
1
)
AS-Interface
FAULT
NSA0_00318
States
Off
Off
Off
Off
Off
Off
Status description
On
On
On
On
On
On
On
Flashing
Flashing
Sensor overload with RESET of slaves
Slave has address = 0
No communication:
Master in STOP mode
Slave not entered in the LPS
Slave has wrong IO&D code
Slave in RESET state
Module completely without voltage
U
Aux
failure Normal operation and
U
Aux
applied
LED
AS-Interface
NSA0_00319
AS-Interface voltage not applied
AS-Interface voltage applied
States
Off
Status description
On
LED
AUX PWR
AS-i / FAULT
NSA0_00313
States
Off
Off
Off
Status description
Sensor overload with RESET of slaves
Slave has address = 0
No communication:
Master in STOP mode
Slave not entered in the LPS
Slave has wrong IO&D code
Slave in RESET state
Module completely without voltage
U
Aux
failure
Normal operation and U
Aux
applied
On
On
On
On
Flashing Flashing
Flashing