CP 343-2 P

6

Overview

The CP 343-2 P is the AS-Interface master for PLC SIMATIC
S7-300 and the distributed I/O device ET 200M. The communi-
cations processor offers the following functions:

• Supports configuration of the AS-Interface network with STEP 7

V5.2 and higher

• Connection of up to 62 AS-Interface slaves and integrated an-

alog value transmission (according to expanded AS-Interface
Specification V2.1)

• Supports all AS-Interface master functions according to ex-

panded AS-Interface Specification V2.1

• Display of errors (incl. AS-Interface voltage errors, configura-

tion errors) through LEDs in the frontplate

• Compact housing in the design of the SIMATIC S7-300

Benefits

• Improved plant documentation and support for servicing

thanks to documentation of the AS-Interface configuration in
the STEP 7 project

• Diagnosis of the AS-Interface network is supported

• Shorter startup times due to easy configuration at the press of

a button

• Flexible decentralized topologies can be constructed by using

this communications processor in the ET 200M DP slave.

• Reduction of standstill or service times in the event of a fault

through LED displays:
- status of the AS-Interface network
- connected slaves and their operational readiness
- monitoring of the AS- Interface voltage level

• Reduced costs for spare parts inventories because the CP can

be used in both the SIMATIC S7-300 and in ET 200M.

• Ideal for complex applications through the connection option

of 62 slaves and integrated analog value processing

Application

The CP 343-2 P is the AS-Interface master connection for
SIMATIC S7-300 and ET 200M. Connection to the AS-Interface
allows access to max. 248 DI/186 DO per CP.

The integrated analog value processing also supports evalua-
tion of very simple analog signals (per CP at max. 31 analog
slaves, each with four channels).

The CP 343-2 P functionality is identical to that of the CP 342-2.
An old S7 user program can therefore be used with the new
CP without any limitations. Also, the AS-Interface configuration
can be downloaded or uploaded with the STEP 7 hardware con-
figuration.

Design

The CP 343-2 P is connected to the S7-300 like an expansion
module. It features:

• Two terminals for direct connection of the AS-Interface cable

• LEDs in the frontplate for displaying the operating status and

operational readiness of all connected and activated slaves

• Pushbuttons for displaying the status information of the slaves,

for switching the operating status and entering the existing
ACTUAL configuration as the SETPOINT configuration

Mode of operation

In I/O mode, the CP 343-2 P reserves 16 bytes in the analog
address space of the SIMATIC S7-300. The I/O data of the
standard slaves or A slaves is stored here. The I/O data of the B
slaves can be accessed using the "read/ write data record “
function.

A and B slaves are slaves in accordance with the extended
AS-Interface specification V2.1. For the AS-Interface master
calls (e.g. Write parameter, read diagnostic values), a Function
Call (FC) is provided on the diskette that accompanies the
manual.

All connected AS-Interface slaves are configured at the press of
a button. No further configuration of the CP is necessary.

Function

The CP 343-2 P supports all functions stipulated in the ex-
panded AS-Interface Specification V2.1. Double address
assignment (A-B) makes it possible to operate up to 62 digital or
31 analog slaves at the AS-Interface. Access to analog values is
easy thanks to the integrated analog value processing.

The CP 343-2 P enables the AS-Interface configuration to be
read out with STEP 7 V5.2 and higher.