AS-Interface Slaves

Module F90

I/O modules for operation in IP20 control cabinet

6

Function

Principle of operation of the 16E module (3RG9 002-0DE00
and 3RG9 004-0DE00)

The 16 inputs are arranged in four groups of four inputs.

Only one group is permitted to be activated at a time. The PLC
activates each group in sequence and reads the four input sig-
nals into the process image of the inputs in each case. The user
program assigns the input information to the appropriate
groups, i .e. the output process image of the PLC must corre-
spond to the set output of the module otherwise input information
will be read in from the wrong group.

When a fault occurs in AS-i transmission, it can take up to three
AS-i cycles (15 ms) until the output image of the slave corre-
sponds to the output image of the master and therefore of the
PLC. It can also take three cycles to transfer the input image of
the slave. If messages to a particular slave are faulty over more
than three consecutive AS-i cycles, the slave outputs a "Config
error" to the master. The input image in the master is set to zeroes
and the fault bit is set in the PLC.

Example: Response of the output image and the input image
in the master and in the slave to faulty AS-Interface transfer

The example shows that the output image and input image are
not consistent in the master and slave until six AS-Interface
cycles have elapsed. The PLC cycle is not synchronous with the
AS-Interface cycle. For this reason, the time that must elapse be-
fore the output image and input image of the master and PLC are
consistent is extended by one AS-Interface cycle and one PLC
cycle respectively.

Formula for the cycle time:
4 · ((6 · 5 ms) + 5 ms + 10 ms) =180 ms

Note 1:
The following function blocks (FBs) are available for
sequence control:

• FB 21 (E16-2433) for the AS-Interface master CP2433

(S5-95 U)

• FB 22 (E16-2430) for the AS-Interface master CP2430

(S5-115 U)

• FC 22 for S7

At least 30 ms must elapse between two function block calls for
a module to ensure that the switching status of the inputs can be
reliably read.

Note 2:
Programming examples can be requested from out
Technical Support, Tel. (+49 91 31) 74 38 33, or down-
loaded from the Internet:

Additional information is available from in the Internet under:

http://www.siemens.de/as-interface

NSA0_00321

AS-

Inter-

face-

cycle

PLC

MasterModule

Note

PIQ

PII

QI

QI

II

1000 xxxx

1

1000 xxxx 0111

xxxx xxxx

xxxx

fault in MC or SR

2

1000 xxxx 0111

xxxx xxxx

xxxx

fault in MC or SR

3

1000 xxxx 0111

EEEE 1000 EEEE I invalid because of

switchover time in modu

4

1000 xxxx 0111

xxxx 1000 EEEE fault in MC or SR

5

1000 xxxx 0111

xxxx 1000 EEEE fault in MC or SR

6

1000 xxxx 0111

EEEE 1000 EEEE no fault in MC or SR

1000 EEEE 0111

Legend:
QI

Output image

II

Input image

MC

Master call

PIQ

Process image of the outputs

PII

Process image of the inputs

SR

Slave response

PLC

Programmable logic controller