As-interface slaves, I/o modules for operation in the field, Digital i/o modules ip67 - k60 – Siemens ISI EN 50295 User Manual
Page 44
Siemens IK PI · 2004
6/44
AS-Interface Slaves
Digital I/O modules IP67 - K60
I/O modules for operation in the field
6
■
Technical specifications
Technical specifications common to all IP67 – K60 digital I/O modules
Operational voltage in accordance
with AS-Interface specification in V
26.5 to 31.6
Input connection
PNP
Inputs
• Sensor supply via AS-Interface
Short-circuit and overload
withstand capability
• Sensors
2- and 3-wire
• Voltage range in V
20 to 30
• Current carrying capacity f
or all inputs (T
u
£ 40 °C) in mA
200
• Switching level High in V
³ 10
• Input current Low/High in mA
£ 1.5 / ³ 6
Outputs
• Type of output
Electronics
• Short-circuit protection
Built-in
• Inductive interference protection
(free-wheeling diode)
Built-in
• External 24 V DC supply voltage
Over black AS-Interface flat cable
• Watchdog
Built-in
AS-Interface certificate
Available (or under application
in the case of new products)
Approvals
UL, CSA, marine certification
(or under application in the case
of new products)
Degree of protection
IP67
Ground connection
PIN 5 of each M12 socket is
connected with the grounding
sheet in the mounting plate
through a pin
Ambient temperature in °C
-25 to +85
Storage temperature in °C
-40 to +85
Status indications
• I/O display
Yellow LED
• Display U
Aux
Green LED
• AS-Interface/diagnostics display
Green/red LED
Connection
Using mounting plate for K60
compact module
Note 1
All K60 compact modules are
supplied with high-grade steel
screws/sockets
Note 2
To supply the output circuit,
an external supplementary
supply (AUX POWER)
of 20 to 30 V DC is necessary.
The supplementary supply must
comply with VDE 0106 (PELV),
Safety Class III.
8 inputs/2 outputs
8 inputs
8 inputs
new
2 A
--
--
A/B slave
Standard slaves
A/B slaves
Special assignment
Y-II assignment
Y-II assignment
3RK2 400–1HQ00–0AA3
3RK1 200–0DQ00–0AA3
3RK2 200–0DQ00–0AA3
Total current input in mA
£ 300
£ 270
£ 270
Socket assignment, inputs
PIN 1 = Sensor supply L+
PIN 2 = Data input II
PIN 3 = Sensor supply L-
PIN 4 = Data input I
PIN 5 = Earth connection
PIN 1 = Sensor supply L+
PIN 2 = Data input II
PIN 3 = Sensor supply L-
PIN 4 = Data input I
PIN 5 = Earth connection
PIN 1 = Sensor supply L+
PIN 2 = Data input II
PIN 3 = Sensor supply L-
PIN 4 = Data input I
PIN 5 = Earth connection
Outputs
• Current carrying capacity per
output in A DC 12 / DC 13 typ.
2
--
--
• Maximum summation current
per module in A
4
--
--
• Socket assignment, outputs
3 = "-"
4 = Output
5 = Ground connection
--
--
I/O configuration
0 (Addr. 1) / 7 (Addr. 2)
0
0
ID/ID2 code
A/E (Addr. 1 and 2)
1/F
A/E
Assignment of data bits
• Socket 1
PIN4 = IN1(D0) (Addr. 1)
PIN2 = IN2(D1) (Addr. 1)
PIN4 = IN1(D0) (Addr. 1)
PIN2 = IN2(D1) (Addr. 1)
PIN4 = IN1(D0) (Addr. 1)
PIN2 = IN2(D1) (Addr. 1)
• Socket 2
PIN4 = IN2(D1) (Addr. 1)
PIN4 = IN2(D1) (Addr. 1)
PIN4 = IN2(D1) (Addr. 1)
• Socket 3
PIN4 = IN3(D2) (Addr. 1)
PIN2 = IN4(D3) (Addr. 1)
PIN4 = IN3(D2) (Addr. 1)
PIN2 = IN4(D3) (Addr. 1)
PIN4 = IN3(D2) (Addr. 1)
PIN2 = IN4(D3) (Addr. 1)
• Socket 4
PIN4 = IN4(D3) (Addr. 1)
PIN4 = IN4(D3) (Addr. 1)
PIN4 = IN4(D3) (Addr. 1)
• Socket 5
PIN4 = IN1(D0) (Addr. 2)
PIN2 = IN2(D1) (Addr. 2)
PIN4 = IN1(D0) (Addr. 2)
PIN2 = IN2(D1) (Addr. 2)
PIN4 = IN1(D0) (Addr. 2)
PIN2 = IN2(D1) (Addr. 2)
• Socket 6
PIN4 = IN2(D1) (Addr. 2)
PIN4 = IN2(D1) (Addr. 2)
PIN4 = IN2(D1) (Addr. 2)
• Socket 7
PIN4 = OUT1(D0) (Addr. 2)
PIN2 = IN3(D2) (Addr. 2)
PIN4 = IN3(D2) (Addr. 2)
PIN2 = IN4(D3) (Addr. 2)
PIN4 = IN3(D2) (Addr. 2)
PIN2 = IN4(D3) (Addr. 2)
• Socket 8
PIN4 = OUT2(D1) (Addr. 2)
PIN2 = IN4(D3) (Addr. 2)
PIN4 = IN4(D3) (Addr. 2)
PIN4 = IN4(D3) (Addr. 2)
Number of I/O sockets
8
8
8
Note
Module requires two addresses
Module requires two addresses
Module requires two addresses