6/118

AS-Interface Slaves

AS-Interface load feeder modules IP20

AS-Interface motor starters and IP20 load feeders

6

Technical specifications

The technical specifications for the load feeders is the same as that specified for the individual devices.
The high short-circuit strength of I

q

= 50 kA also applies.

Load feeders modules IP20

2I/1O

4I/2O

2I/1OR

3I/2OR

3RK1 400-1KG01-0AA1

3RK1 400-1MG01-0AA1

3RK1 402-3KG02-0AA1

3RK1 402-3LG02-0AA1

I/O configuration (hex)

3

7

3

7

ID code (hex)

F

F

F

F

Supply voltage for electronics
and inputs in V
(checkbacks from the auxiliary
contacts of the controlgear)
via AS-Interface data cable

26.5 to 31.6 (in accordance with AS-Interface specification)

Power consumption of AS-Interface
in mA

8 to 12

Temperature range

• Operating temperature T

u

in °C

0 to +55

• Storage temperature in °C

-40 to +85

Degree of protection

IP20

Inputs

Polarity reversal protection

Built-in

Max. input current in mA

6

Max. permissible cable length
between IN + and an input in m

0.4

Outputs

External supply voltage for outputs
in V
(triggering of the contactor coils)
via auxiliary power

24 DC

Max. 230 AC

Current carrying capacity I

e

in A

0.5 (DC-13/DC-14)

3 (AC-15); 0.1 (DC-13 at 220 V)

Summation current (thermal) I

th

in A 2

3

Polarity reversal protection

Built-in

Not required

Short-circuit protection

Built-in

No

Inductive interference protection
(free-wheeling diode)

Built-in

Not required

Watchdog

(shutdown of outputs in case
of AS-Interface fault)

Built-in

Diagnostics

Via LED at the housing

Auxiliary voltage applied
AS-Interface communication OK
AS-Interface communication faulty
Station address = 0 (module not addressed)

Output activated
AS-Interface communication OK
AS-Interface communication faulty
Station address = 0 (module not addressed)

Conductor cross-sections

Plug connector for AS-Interface and
auxiliary power in mm

2

0.5 to 0.75 (flexible)

Cage Clamp for I/O wiring in mm

2

0.8 to 2.5 (flexible, without end sleeve)

Power connector, 5-pole in mm

2

0.5 to 2.5
AWG 28 to 12

PE/N conductor wiring on carrier
in mm

2

2.5 flexible
AWG 13

Addressing

After the 15th addressing, the module keeps the last address