As-interface slaves, As-interface motor starters and ip20 load feeders, As-interface load feeder modules ip20 – Siemens ISI EN 50295 User Manual
Page 118
Siemens IK PI · 2004
6/118
AS-Interface Slaves
AS-Interface load feeder modules IP20
AS-Interface motor starters and IP20 load feeders
6
■
Technical specifications
The technical specifications for the load feeders is the same as that specified for the individual devices.
The high short-circuit strength of I
q
= 50 kA also applies.
Load feeders modules IP20
2I/1O
4I/2O
2I/1OR
3I/2OR
3RK1 400-1KG01-0AA1
3RK1 400-1MG01-0AA1
3RK1 402-3KG02-0AA1
3RK1 402-3LG02-0AA1
I/O configuration (hex)
3
7
3
7
ID code (hex)
F
F
F
F
Supply voltage for electronics
and inputs in V
(checkbacks from the auxiliary
contacts of the controlgear)
via AS-Interface data cable
26.5 to 31.6 (in accordance with AS-Interface specification)
Power consumption of AS-Interface
in mA
8 to 12
Temperature range
• Operating temperature T
u
in °C
0 to +55
• Storage temperature in °C
-40 to +85
Degree of protection
IP20
Inputs
Polarity reversal protection
Built-in
Max. input current in mA
6
Max. permissible cable length
between IN + and an input in m
0.4
Outputs
External supply voltage for outputs
in V
(triggering of the contactor coils)
via auxiliary power
24 DC
Max. 230 AC
Current carrying capacity I
e
in A
0.5 (DC-13/DC-14)
3 (AC-15); 0.1 (DC-13 at 220 V)
Summation current (thermal) I
th
in A 2
3
Polarity reversal protection
Built-in
Not required
Short-circuit protection
Built-in
No
Inductive interference protection
(free-wheeling diode)
Built-in
Not required
Watchdog
(shutdown of outputs in case
of AS-Interface fault)
Built-in
Diagnostics
Via LED at the housing
Auxiliary voltage applied
AS-Interface communication OK
AS-Interface communication faulty
Station address = 0 (module not addressed)
Output activated
AS-Interface communication OK
AS-Interface communication faulty
Station address = 0 (module not addressed)
Conductor cross-sections
Plug connector for AS-Interface and
auxiliary power in mm
2
0.5 to 0.75 (flexible)
Cage Clamp for I/O wiring in mm
2
0.8 to 2.5 (flexible, without end sleeve)
Power connector, 5-pole in mm
2
0.5 to 2.5
AWG 28 to 12
PE/N conductor wiring on carrier
in mm
2
2.5 flexible
AWG 13
Addressing
After the 15th addressing, the module keeps the last address