beautypg.com

As-interface slaves, I/o modules for operation in the field – Siemens ISI EN 50295 User Manual

Page 66

background image

Siemens IK PI · 2004

6/66

AS-Interface Slaves

Digital I/O modules IP67 - application modules

I/O modules for operation in the field

6

Technical specifications (continued)

2 inputs/2 outputs

Relay

PNP transistor

NPN transistor

3RG9 001–0AC00

3RG9 001–0CC00

3RG9 001–0AM00

3RK1 400–1BQ01–0AA3

Slave type

Standard slaves

Operational voltage in accordance
with AS-Interface specification in V

26.5 to 31.6

Total current input in mA

£ 140

£ 270

£ 270

£ 290

Input connection

PNP

NPN

Inputs

• Sensor supply via AS-Interface

Short-circuit and overload proof

• Sensors

2- and 3-wire

• Voltage range in V

20 to 30

20 to 27

• Current carrying capacity

for all inputs (T

u

£ 40 °C) in mA

100

200

• Connection of sensors

2- and 3-wire system

• Switching level High in V

³ 10

• Input current Low/High in mA

£ 1.5 / ³ 5

Outputs

• Type of output

Relay

Electronics

• Current carrying capacity per

output in A DC 12 / DC 13 typ.

1 (DC 12)
0.5 (DC 13 24 V)

2

1

• Maximum summation current

per module in A

2

• Short-circuit protection

Built-in

• Inductive interference protection

(free-wheeling diode)

Built-in

• External 24 V DC supply voltage

Via M 12 plug

24 V DC via black flat
cable

Via M 12 plug

24 V DC via black flat
cable

• Watchdog

Not available

Built-in

Connection of AS-Interface

EMI

EEMI

EMI

EEMI

I/O configuration

3

ID code

0

1

Assignment of data bits

• Socket 1

Input (D0)

PIN4 = IN1 (D0)
PIN2 = IN2 (D1)

• Socket 2

Input (D1)

PIN4 = IN2(D1)

• Socket 3

Output (D2)

PIN4 = OUT1 (D2)
PIN2 = OUT2 (D3)

• Socket 4

Output (D3)

PIN4 = OUT2 (D3)

AS-Interface certificate

Yes

Approvals

UL, CSA, ship building

Degree of protection

IP67

Ambient temperature in °C

-25 to +85

Storage temperature in °C

-40 to +85

Number of I/O sockets

4

I/O display

Yellow LED

AS-Interface display

Green LED

Red/yellow/green LED

AS-Interface/diagnostics display

Without LED

"AS-i" LED:
green = OK
red =
no data communication
flashing red/yellow =
null address
flashing red =
overload sensor

Connection

Via contact pin on the FK or Pg coupling module

Note 1

To supply the output circuit, an external supplementary supply (AUX POWER) of 20 to 30 V DC is necessary.
The supplementary supply must comply with VDE 0106 (PELV), Safety Class III.

Note 2

In the event of a commu-
nications failure, the relay
outputs remain in the
current switching state.